TESTING FOR EMERGENCY LUMINAIRES
Recommended routine test procedure in accordance with BS5266
•
Daily check
–
check LED charge indicator is illuminated
•
Monthly functional test - simulate a mains supply failure for approx. 30 seconds by operation of key
switch or switching off circuit breaker. Ensure normal supply is restored after test and ensure
charge indicator is illuminated
•
Annual 3-hour duration test - simulate a mains supply failure for 3-hour continuous test by
operation of key switch or switching off circuit breaker. Ensure normal supply is restored after test
and ensure charge indicator is illuminated
•
If the luminaire fails any of the above tests, please contact a qualified electrician. See below for test
record sheet