background image

INSTALLATION & MAINTENANCE MANUAL 

 

These instructions should be read carefully and retained after installation by the end user for future reference 

and maintenance. 

These instructions should be used to aid installation of the following products: 

FLN10 / FLN20 / FLN30 / FLN50 / FLNMIC / FLNPIR 
SAFETY 

 

This product must be installed in accordance with the latest edition of the IEE Wiring Regulations 

(BS7671) and current Building Regulations. If in any doubt, consult a qualified electrician 

 

Please isolate mains prior to installation or maintenance 

 

Check the total load on the circuit (including when this product is fitted) does not exceed the rating of 

the circuit cable, fuse or circuit breaker 

 

Please note the IP (Ingress Protection) rating of this product when deciding the location for installation 

 

Do not overload this accessory or subject it to conditions outside its rating 

 

The FLNxx fittings are Class I and must be earthed 

 

This FLNMIC and FLNPIR accessories are Class II double insulated 

 

This product series is IP65 rated 

INSTALLATION 

Note - Microwave sensors may not be suitable for all installations, for example enclosed spaces, as they are 

able to detect movement through non-metallic surfaces like plasterboard and thin doors. Both sensors can be 

falsely triggered by changes in temperature, therefore should not be installed near sources of heat such as 

boiler flues. 

 

Provide power to the required point of installation (refer to BS7671 for correct cabling methods). 

Suitable IP rated junction boxes should be used where required 

 

Round cable should be used for the mains supply, with an outer diameter of 7-9mm and a CSA of up 

to 1.5mm

2

. The use of flat cable will cause water ingress to the fitting. A drip loop should be left on the 

incoming cable 

 

Using the bracket as a template, mark the location for, and drill the fixing holes ensuring not to infringe 

with any gas / water pipes or electrical cables. This can be done without removing the bracket from the 

fitting (see Fig. 1) 

 

Fig. 1 

 

Fix the luminaire to a suitable solid surface using the wall plugs and screws provided 

 

Tilt so that the cable entry points are accessible 

 

Unscrew the sealing nut from the compression gland (see Fig. 2) and fit it over the supply cable 

INSTALLATION

Note - Microwave sensors may not be suitable for all installations, for example 
enclosed spaces, as they are able to detect movement through non-metallic surfaces 
like plasterboard and thin doors. Both sensors can be falsely triggered by changes in 
temperature, therefore should not be installed near sources of heat such as boiler flues.

• Provide power to the required point of installation (refer to BS7671 for correct cabling 
   methods). Suitable IP rated junction boxes should be used where required
• Round cable should be used for the mains supply, with an outer diameter of 5-7.4mm 
   and a CSA of up to 1.5mm

2

. The use of flat cable will cause water ingress to the fitting. A 

   drip loop should be left on the incoming cable
• Using the bracket as a template, mark the location for, and drill the fixing holes ensuring 
   not to infringe with any gas/water pipes or electrical cables. This can be done without 
   removing the bracket from the fitting (see Fig. 1)

Fig. 1

Summary of Contents for FLN10

Page 1: ...INSTALLATION MAINTENANCE MANUAL FLN10 FLN20 FLN30 FLN50 FLNMIC FLNPIR...

Page 2: ...ng Regulations If in any doubt consult a qualified electrician Please isolate mains prior to installation or maintenance Check the total load on the circuit including when this product is fitted does...

Page 3: ...supply with an outer diameter of 7 9mm and a CSA of u to 1 5mm2 The use of flat cable will cause water ingress to the fitting A drip loop should be left on th incoming cable Using the bracket as a tem...

Page 4: ...ber gasket in place see Fig 2 and pass the supply cable through the compression gland Prepare the supply cable as shown by stripping back the outer sheath and basic insulation to the correct length se...

Page 5: ...pply cable through the compression gland Prepare the supply cable as shown by stripping back the outer sheath and basic insulation to the correct length see Fig 3 Fig 3 Connect the supply cable ensuri...

Page 6: ...tection area is covered Then set the TIME and LUX controls to the desired settings PIR MICROWAVE SENSOR ACCESSORY Fig 4 Align the pins on the sensor push onto the fitting and tighten ensuring a good s...

Page 7: ...for where facilities exist This product must be disconnected from the circuit if subjected to any high voltage or insulation resistance testing Irreparable damage will occur if this instruction is no...

Page 8: ...s product should fail within its warranty period it should be returned to the place of purchase for a free of charge replacement ML Accessories does not accept responsibility for any installation cost...

Reviews: