• Switch on and check for correct operation ensuring the green indicator LED is illuminated
• See below for operation of the self-test function
• We recommend, on commissioning the installation, a minimum charge period of 24 hours before carrying
out an emergency duration test
Fig. 3
Fig. 3
•
Select the required sensor settings (see below)
•
Switch on and check for correct operation ensuring the green indicator LED is illuminated
•
See below for operation of the self-test function
•
We recommend, on commissioning the installation, a minimum charge period of 24 hours before
carrying out an emergency duration test
SELF-TEST FUNCTION
When first connected to the mains supply, the fitting will carry out an initial 3-second function test. Any faults
will be indicated by the bi-colour LED indicator.
This product is programmed to carry out its own self-test operation according to the following programme:
The test button on the side of the fitting can also be used to initiate functional testing as required – the
luminaire will go into emergency mode while the test button is held in.
Following self-tests, the unit will revert to charging mode, and any faults will be indicated by the bi-colour
LED indicator as follows:
SELF-TEST FUNCTION
When first connected to the mains supply, the fitting will carry out an initial 3-second function test. Any faults will
be indicated by the bi-colour LED indicator.
This product is programmed to carry out its own self-test operation according to the following programme:
Every 30 days
10-second function test
Every 180 days
3-hour duration test
The test button on the side of the fitting can also be used to initiate functional testing as required – the luminaire
will go into emergency mode while the test button is held in.
Following self-tests, the unit will revert to charging mode, and any faults will be indicated by the bi-colour LED
indicator as follows:
LED indicator
Status
Slow flash green (3 sec on, 1 sec off)
Charging
Solid green
Fully charged
Fast flash green (0.1 sec on, 0.1 sec off)
Function test underway
Slow flash green (1 sec on, 1 sec off)
Duration test underway
Solid red
Lamp fault (open circuit / short circuit)
Slow flash red (1 sec on, 1 sec off)
Battery fault or failed duration test
Indicator off
Emergency mode
To clear a fault indication, switch off the power to the luminaire and then hold the test button for 10 seconds.
WARNING
This product must be disconnected from the circuit if subjected to any high voltage or insulation resistance
testing. Irreparable damage will occur if this instruction is not followed.
GENERAL
This product contains a light source of energy efficiency class D to Regulation (EU) No. 2019/2015 and (UK)
2021 No. 1095.
This product contains a non-replaceable LED light source and a control gear which can be replaced by a
professional.
Clean with a soft dry cloth only, do not use aggressive cleaning products or solvents which may damage the
product.
Installing in areas where the temperature consistently drops below 0°C may shorten the battery life.