background image

• Switch on and check for correct operation ensuring the green indicator LED is illuminated
• See below for operation of the self-test function
• We recommend, on commissioning the installation, a minimum charge period of 24 hours before carrying 
   out an emergency duration test

Fig. 3

 

 

Fig. 3 

 

Select the required sensor settings (see below) 

 

Switch on and check for correct operation ensuring the green indicator LED is illuminated 

 

See below for operation of the self-test function 

 

We recommend, on commissioning the installation, a minimum charge period of 24 hours before 

carrying out an emergency duration test 

 

 

 

SELF-TEST FUNCTION

When first connected to the mains supply, the fitting will carry out an initial 3-second function test. Any faults 
will be indicated by the bi-colour LED indicator. 
This product is programmed to carry out its own self-test operation according to the following programme:

The test button on the side of the fitting can also be used to initiate functional testing as required – the 
luminaire will go into emergency mode while the test button is held in.
Following self-tests, the unit will revert to charging mode, and any faults will be indicated by the bi-colour 
LED indicator as follows:

 

SELF-TEST FUNCTION 

When first connected to the mains supply, the fitting will carry out an initial 3-second function test. Any faults will 

be indicated by the bi-colour LED indicator.  

This product is programmed to carry out its own self-test operation according to the following programme: 

Every 30 days 

10-second function test 

Every 180 days 

3-hour duration test 

The test button on the side of the fitting can also be used to initiate functional testing as required – the luminaire 

will go into emergency mode while the test button is held in. 

Following self-tests, the unit will revert to charging mode, and any faults will be indicated by the bi-colour LED 

indicator as follows: 

LED indicator 

Status 

Slow flash green (3 sec on, 1 sec off) 

Charging 

Solid green 

Fully charged 

Fast flash green (0.1 sec on, 0.1 sec off) 

Function test underway 

Slow flash green (1 sec on, 1 sec off) 

Duration test underway 

Solid red 

Lamp fault (open circuit / short circuit) 

Slow flash red (1 sec on, 1 sec off) 

Battery fault or failed duration test 

Indicator off 

Emergency mode 

 To clear a fault indication, switch off the power to the luminaire and then hold the test button for 10 seconds. 

WARNING 

This product must be disconnected from the circuit if subjected to any high voltage or insulation resistance 

testing. Irreparable damage will occur if this instruction is not followed. 

GENERAL 

This product contains a light source of energy efficiency class D to Regulation (EU) No. 2019/2015 and (UK)

 

2021 No. 1095. 

This product contains a non-replaceable LED light source and a control gear which can be replaced by a 

professional. 

 

 

Clean with a soft dry cloth only, do not use aggressive cleaning products or solvents which may damage the 

product. 

Installing in areas where the temperature consistently drops below 0°C may shorten the battery life. 

Summary of Contents for BATSCWST4

Page 1: ...INSTALLATION MAINTENANCE MANUAL BATSCWST4 BATSCWST5 BATSCWST6...

Page 2: ...or maintenance Check the total load on the circuit including when this luminaire is fitted does not exceed the rating of the circuit cable fuse or circuit breaker Please note the IP Ingress Protection...

Page 3: ...s ensuring not to infringe with any gas or electrical cables The fitting can also be mounted over conduit boxes the distance betw centres is 600mm Feed the mains cable through the cable entry point an...

Page 4: ...lowing programme The test button on the side of the fitting can also be used to initiate functional testing as required the luminaire will go into emergency mode while the test button is held in Follo...

Page 5: ...luminaire and then hold the test button for 10 seconds WARNING This product must be disconnected from the circuit if subjected to any high voltage or insulation resistance testing Irreparable damage...

Page 6: ...ium Ion and must be disposed of correctly Please contact the local authorities for the disposal of this toxic waste WARRANTY This product has a warranty of 5 years excluding battery from date of purch...

Page 7: ...l supply is restored after test and check status of bi colour LED indicator 3 hour duration test the luminaire will perform this function without any action from the user Alternatively simulate a main...

Page 8: ...operation of key switch or switching off circu breaker Ensure normal supply is restored after test and check status of bi colour LED indicator If the luminaire fails any of the above tests please cont...

Page 9: ...y UK Manufacturer ML Accessories Ltd Unit E Chiltern Park Boscombe Road Dunstable LU5 4LT www mlaccessories co uk EU Authorised Representative nnuks Holding GmbH Niederkasseler Lohweg 18 40547 D sseld...

Reviews: