TEST RECORD
Recommended routine test procedure in accordance with BS5266:
• Daily check – check status of bi-colour LED indicator
• Monthly functional test – the luminaire will perform this function without any action from the user.
Alternatively, simulate a mains supply failure for approx. 30 seconds by operation of key switch, switching off
circuit breaker or using test button. Ensure normal supply is restored after test and check status of bi-colour
LED indicator
• 3-hour duration test – the luminaire will perform this function without any action from the user.
Alternatively, simulate a mains supply failure for 3-hour continuous test by operation of key switch, or
switching off circuit breaker. Ensure normal supply is restored after test and check status of bi-colour LED
indicator
• If the luminaire fails any of the above tests, please contact a qualified electrician. Results should be recorded,
even when obtained via the self-test function. See below for test record sheet