7BChapter Four: Operation
74BConnection Object
63
ID # (dec)
Value
16
consumed_connection_path
Empty
No specified default. An
implementation
must
choose an
Application Object to reference by
default and initialize this attribute
accordingly.
17
production_inhibit_time
0
Default is no inhibit time.
* Refer to the ODVA “DeviceNet Specification,” Volume II [2], for information on User and
Calibration Mode access.
Table 31: Poll Response Setup of the Produced_Connection_Path
Assembly
Instance
Produced_Connection_Path
(hex bytes)
2
(INT) 20 04 24 02 30 03
5
(REAL) 20 04 24 05 30 03
The poll response is identified in the Device Configuration Object (page 71).
Master Poll Request Message
Note
The master’s poll request message does not report any data. The response returns
the CAN Identifier only [1].
Slave Poll Response Assembly Instance 2
Note
There are two poll response messages from the slave. The poll response reported
is defined in the Device Configuration Object (page 71). The data for each
response is stored in the Assembly Object (page 58).
Poll assembly instance 2 reports the exception status from the S-Device Supervisor Object (refer
to
Exception Status
, page 75) and the 16-bit pressure value from the S-Analog Sensor Object
(refer to
Reporting the Pressure Value
, page 31) in the format shown in Table 32. Refer to
Assembly Object Instance ID #02 in Table 25, page 58.