SECTION 3
OPERATION
30
Setting example
1) To stop the boiler all the day
ON time ...................... 24:00
OFF time .................... 0:00
2) To fire up the boiler all the day
ON time ...................... 0:00
OFF time .................... 24:00
3) To fire up the boiler from 8:00 to 17:00
ON time ...................... 8:00
OFF time .................... 17:00
4) To turn on the boiler at a fixed time (8:00 in example), and stop by a customer.
ON time ...................... 8:00
OFF time .................... 13:00 (Set a time when the boiler should be stopped)
The timer operation causes the boiler to start firing at 8:00. Be sure to press “TIMER” between
8:00 and 13:00 to stop timer operation. (Disabling the timer operation allows the boiler to
perform combustion after 13:00.)
To stop boilers, press the “TIMER” switch to activate the timer operation.
5) To turn on the boiler by a customer and stop at a fixed time (17:00 in example)
ON time ...................... 13:00 (Set a time when the boiler should be in operation)
OFF time .................... 17:00
To start boilers, press the “TIMER” switch before 13:00 to stop the timer operation. (Stopping
the timer operation allows the boiler to start combustion.)
Press the “TIMER” switch between 13:00 and 17:00 to activate the timer.
(The boiler combustion continues as the time is after the ON time.)
The timer function causes the boiler to stop at 17:00.