2. Installation location 

Fig. 2-3

Fig. 2-2

Fig. 2-4

Fig. 3-1

3. Installation procedures

•  Be sure to install the unit in a solid, level surface to prevent rattling noises during 

operation. (Fig. 3-1)

<Foundation specifications>

Foundation bolt

M10 (3/8")

Thickness of concrete

120 mm

Length of bolt

70 mm

Weight-bearing capacity

320 kg

•  Make sure that the length of the foundation bolt is within 30 mm from the surface 

of the base.

•  Secure the base of the unit firmly with 4 M10 foundation bolts in solid locations. 

Installing the outdoor unit

•  Do not block the vent. If the vent is blocked, operation will be hindered and the unit 

may breakdown.

• If the additional fixation of the unit is necessary, use the installation holes on the 

back of the unit to attach wires, etc. with self-tapping screws (ø5 × 15 mm or less).

 Warning:

• The unit must be securely installed on a structure that can sustain its weight. 

If the unit is mounted on an unstable structure, it may fall down and cause 

damage or injuries.

•  The unit must be installed according to the instructions in order to minimize 

the risk of damage by earthquakes, typhoons, or strong winds. An improp

-

erly installed unit may fall down and cause damage or injuries.

 

* Figures in parentheses are for 112/140 unit types.

(mm)

2.3. 

Windy location installation

When installing the outdoor unit on a rooftop or other location where the unit is 

exposed to strong wind, do not face the air outlet of the unit directly into the winds. 

Strong wind entering the air outlet may impede the normal airflow and it may result 

in a malfunction.

The following shows three examples of precautions against strong winds.

1

  Face the air outlet towards the nearest available wall keeping about 50 cm dis-

tance. (Fig. 2-2)

2

  Install an optional air guide if the unit is installed in a location where strong winds 

such as a typhoon, etc. may directly blow to the air outlet. (Fig. 2-3)

 

A

   Air  guide

3

  Position the unit so that the outlet air can blow at right angle to the seasonal wind 

direction, if possible. (Fig. 2-4)

 

B

   Wind  direction

A

 M10 (3/8") bolt

B

 Base

C

 As long as possible

D

 Vent

E

 Set deep in the ground

F

 Max.30

G

 Min.360 (430)

H

 Min.10

2.4. NECESSARY SPACE TO INSTALL

2.4.1. When installing a single outdoor unit (Refer to the last page)

Minimum dimensions are as follows, except for Max., meaning Maximum dimen-

sions, indicated.

The figures in parentheses are for 112/140 models.

Refer to the figures for each case.

1

 Obstacles at rear only (Fig. 2-5)

2

 Obstacles at rear and above only (Fig. 2-6)

  •   Do not install the optional air outlet guides for upward airflow.

3

 Obstacles at rear and sides only (Fig. 2-7)

4

 Obstacles at front only (Fig. 2-8)

  *   When using an optional air outlet guide, the clearance for 112/140 models is 500 mm or 

more.

5

 Obstacles at front and rear only (Fig. 2-9)

  *   When using an optional air outlet guide, the clearance for 112/140 models is 500 mm or 

more.

6

 Obstacles at rear, sides, and above only (Fig. 2-10)

  •   Do not install the optional air outlet guides for upward airflow.

2.4.2. When installing multiple outdoor units (Refer to the last page)

Leave 10 mm space or more between the units.

The figures in parentheses are for 112/140 models.

Refer to the figures for each case.

1

 Obstacles at rear only (Fig. 2-11)

2

 Obstacles at rear and above only (Fig. 2-12)

  •   No more than 3 units must be installed side by side. In addition, leave space as shown.
  •   Do not install the optional air outlet guides for upward airflow.

3

 Obstacles at front only (Fig. 2-13)

  *   When using an optional air outlet guide, the clearance for 112/140 models is 1000 mm or 

more.

4

 Obstacles at front and rear only (Fig. 2-14)

  *   When using an optional air outlet guide, the clearance for 112/140 models is 1000 mm or 

more.

5

 Single parallel unit arrangement (Fig. 2-15)

  *   When using an optional air outlet guide installed for upward airflow, the clearance is 500 

(1000) mm or more.

6

 Multiple parallel unit arrangement (Fig. 2-16)

  *   When using an optional air outlet guide installed for upward airflow, the clearance is 1000 

(1500) mm or more.

7

 Stacked unit arrangement (Fig. 2-17)

  •   The units can be stacked up to 2 units high.
  •   No more than 2 stacked units must be installed side by side. In addition, leave space as 

shown.

01_BH79D532H01_EN.indd   4

2015/06/10   15:17:17

Summary of Contents for PUHZ-HW112YHA

Page 1: ...oor voordat u met het installeren van het buitenapparaat begint Het Engels is het origineel De andere taalversies zijn vertalingen van het origineel MANUAL DE INSTALACI N Para un uso correcto y seguro...

Page 2: ...hock or fire If the air to water heat pump needs to be repaired or moved ask an installer or an authorized technician After installation has been completed make sure that refrigerant does not leak If...

Page 3: ...risk of an electric shock For the power lines use standard cables of sufficient capacity Otherwise it may cause a short circuit overheating or fire When installing the power lines do not apply tensio...

Page 4: ...at right angle to the seasonal wind direction if possible Fig 2 4 B Wind direction A M10 3 8 bolt B Base C As long as possible D Vent E Set deep in the ground F Max 30 G Min 360 430 H Min 10 2 4 NECES...

Page 5: ...t water gauge pressure must be between 0 0 3 MPa Use the inlet water with a temperature lower than 55 C Note The water velocity in pipes should be kept within certain limits of material to avoid erosi...

Page 6: ...3 The figures are NOT always against the ground S3 terminal has 24 VDC against S2 terminal However between S3 and S1 these terminals are NOT electrically insulated by the transformer or other device...

Page 7: ...r the compressor starts to warm up once power is supplied After supplying power for the times indicated below re move the wires from the compressor and measure the insulation resistance again The insu...

Page 8: ...ni ej s przeznaczone do zastosowa w rodowisku mieszkalnym handlowym i lekko uprzemys owionym MITSUBISHI ELECTRIC PUHZ W50VHA2 PUHZ W50VHA2 BS PUHZ W112VHA PUHZ W112VHA BS PUHZ HW112YHA2 PUHZ HW112YHA2...

Page 9: ...wiadcza na swoj wy czn odpowiedzialno e klimatyzatory i pompy ciep a opisane poni ej s przeznaczone do zastosowa w rodowisku mieszkalnym handlowym i lekko uprzemys owionym MITSUBISHI ELECTRIC PUHZ W85...

Page 10: ...anv ndare i aff rer inom l tt industri och p lantbruk eller f r kommersiell anv ndning av lekm n NEDERLANDS Het Engels is het origineel De andere taalversies zijn vertalingen van het origineel VOORZIC...

Page 11: ...obsluhovat laici POLSKI J zykiem orygina u jest j zyk angielski Inne wersje j zykowe stanowi t umacze nie orygina u UWAGA Wyciek czynnika ch odniczego mo e spowodowa uduszenie Nale y zapewni wentylacj...

Page 12: ...1000 2000 300 1000 1500 500 800 150 1000 1500 400 600 2000 3000 300 500 Fig 2 5 Fig 2 6 Fig 2 7 Fig 2 8 Fig 2 9 Fig 2 10 Fig 2 11 Fig 2 12 Fig 2 13 Fig 2 14 Fig 2 15 Fig 2 16 Fig 2 17 100 200 300 100...

Page 13: ...ntact address telephone number on this manual before handing it to the customer This product is designed and intended for use in the residential commercial and light industrial environment The product...

Reviews: