background image

18

E6

E7

Check code

Abnormal point and detection method 

Cause

Countermeasure

Fb

E1

or

E2

1

 Contact failure, short circuit or, 

miswiring (converse wiring) of 

indoor/outdoor unit connecting 

wire

2

 Defective transmitting receiving 

circuit of indoor controller board

3

 Defective transmitting receiving 

circuit of indoor controller board

4

 Noise has entered into indoor/ 

outdoor unit connecting wire.

  Check LED display on the outdoor control 

circuit board. (Connect A-control service 

tool, PAC-SK52ST.)

  Refer to the outdoor unit service manual.

Check disconnection or looseness of indoor/ 

outdoor unit connecting wire of indoor unit or 

outdoor unit.

Check all the units in case of twin triple 

indoor unit system.

2

4

 Turn the power off, and on again to 

check. If abnormality generates again, 

replace indoor controller board or outdoor 

controller circuit board.

Note:

Other indoor controller board may have defect 

in the case of twin triple indoor unit system.

Indoor/outdoor unit communication 

error (Transmitting error)

Abnormal if “1” receiving is detected 30 

times continuously though indoor controller 

board has transmitted “0”.

1

 Defective transmitting receiving 

circuit of indoor controller board 

2

 Noise has entered into power 

supply.

3

 Noise has entered into outdoor 

control wire.

1

3

 Turn the power off, and on again to 

check. If abnormality generates again, 

replace indoor controller board.

Indoor/outdoor unit communication 

error (Signal receiving error)

1

 Abnormal if indoor controller board 

cannot receive any signal normally for 6 

minutes after turning the power on.

2

 Abnormal if indoor controller board 

cannot receive any signal normally for 3 

minutes. 

3

 Consider the unit abnormal under the 

following condition: When 2 or more 

indoor units are connected to an outdoor 

unit, indoor controller board cannot 

receive a signal for 3 minutes from 

outdoor controller circuit board, a signal 

which allows outdoor controller circuit 

board to transmit signals. 

Indoor controller board

Abnormal if data cannot be read normally 

from the nonvolatile memory of the indoor 

controller board.

1

 Defective indoor controller 

board

1

 Replace indoor controller board.

Remote controller control board

1

 Abnormal if data cannot be read nor-

mally from the nonvolatile memory of the 

remote controller control board.

    (Check code: E1)

2

 Abnormal if the clock function of remote 

controller cannot be operated normally.

    (Check code: E2)

1

 Defective remote controller

1

 Replace remote controller.

E3

or

E5

Remote controller transmission error(E3)/

signal receiving error(E5)

1

 Abnormal if remote controller could not 

find blank of transmission path for 6 

seconds and could not transmit.

    (Check code: E3)  

2

 Remote controller receives transmitted 

data at the same time and compares the 

received and transmitted data. Abnormal 

if these data are judged to be different 

30 continuous times. (

Check code

e: E3) 

1

 Abnormal if indoor controller board could 

not find blank of transmission path.

   (Check code: E5)   

2

 Indoor controller board receives 

transmitted data at the same time and 

compares the received and transmitted 

data. Abnormal if these data are judged 

to be different 30 continuous times. 

(

Check code

: E5)

1

 Set a remote controller to main, and the 

other to sub.

2

 Remote controller is connected with only one 

indoor unit.

3

 The address changes to a separate setting.

4

Diagnose remote controller.

a) When “RC OK” is displayed, remote con

-

trollers have no problem.

Turn the power off, and on again to check.

When becoming abnormal again, replace 

indoor controller board.

b) When “RC NG” is displayed, replace 

remote controller.

c) When “RC E3” or “ERC 00-66” is dis

-

played, noise may be causing abnormal

-

ity.

1

 2 remote controllers are set as 

“main.”

(In case of 2 remote controllers)

2

 Remote controller is connected 

with 2 indoor units or more.

3

 Repetition of refrigerant address

4

 Defective transmitting receiving 

circuit of remote controller

5

 Defective transmitting receiving 

circuit of indoor controller board

6

 Noise has entered into 

transmission wire of remote 

controller.

OCH452B

Summary of Contents for PKA-RP100KALR1.TH

Page 1: ...N OFF TEMP PARTS CATALOG OCB452 INDOOR UNIT PKA RP60KAL TH PKA RP60KAL TH ER PKA RP60KALR1 TH PKA RP60KALR1 TH ER PKA RP71KAL TH PKA RP71KAL TH ER PKA RP71KALR1 TH PKA RP71KALR1 TH ER PKA RP100KAL TH...

Page 2: ...ZRP60 71VHA PUHZ RP35 50 60 71VHA4 PUHZ RP100 125 140VKA PUHZ RP100 125 140 200 250YKA PU H P71 100VHA PU H P71 100 125 140YHA PUHZ HRP100VHA2 PUHZ HRP100YHA2 PUHZ ZRP100VKA2 UK PUHZ ZRP100YKA2 UK PUH...

Page 3: ...com pressor Do not use a charging cylinder If a charging cylinder is used the composition of refrigera nt will change and the efficiency will be lowered Flare tool Electronic refrigerant charging scal...

Page 4: ...rse flow check Attach on vacuum pump 6 Refrigerant charge base 7 Refrigerant cylinder Only for R410A Top of cylinder Pink Cylinder with syphon 8 Refrigerant recovery equipment 1 Cautions for service 1...

Page 5: ...isplays whether timer is on or off Buttons used to set the hour and minute of the current time and timer settings h and min buttons display display FAN SPEED display indicates which fan speed has been...

Page 6: ...46 kW A kW K min CFM Pa mmAq kW dB mm in mm in mm in mm in kg lb Mode Power supply phase cycle voltage Input Running current External finish Panel Heat exchanger Fan Fan drive o No Fan motor output A...

Page 7: ...20 230 240V 50Hz 10 0 15 0 20 0 25 0 30 0 35 0 40 0 45 0 50 0 55 0 60 0 65 0 70 0 63 125 250 500 1k 2k 4k 8k NC 60 NC 50 Octave band pressure level dB 0dB 20 Pa Approximate minimum audible limit on co...

Page 8: ...T STAND BY lamp Receiver Knockout hole for right piping Mount board Right side 444 Gas pipe 482 Liquid pipe 585 Drain hose Filter hook Under side Vane auto Knockout hole for lower piping Louver manual...

Page 9: ...te controller transmission line TB6 TH2 SW1 TH5 SW2 SWE LEGEND TO OUTDOOR UNIT 5 3 1 3 1 CN01 BLK ORN YLW BLU RED GRN YLW I B w1 Fig 1 I B TB2 POWER SUPPLY 1PHASE 230V 50Hz ORN ORN YLW BRN TB4 INDOOR...

Page 10: ...low in heating Strainer 50 Strainer 50 Heat exchanger Refrigerant GAS pipe connection Flare Refrigerant LIQUID pipe connection Flare REFRIGERANT SYSTEM DIAGRAM 8 PKA RP60KAL TH PKA RP71KAL TH PKA RP10...

Page 11: ...ording to 9 4 TROUBLESHOOTING BY INFERIOR PHENOMENA The trouble is not reoccurring Logged Not logged 1Consider the temporary defects such as the work of protection devices in the refrigerant circuit i...

Page 12: ...s cancelled Procedure 1 Press the CHECK button twice 2 Press the temperature buttons 3 Point the remote controller at the sensor on the indoor unit and press the HOUR button 4 Point the remote control...

Page 13: ...Number of times Wireless remote controller Wired remote controller 1 P1 Intake sensor error P9 Pipe TH5 sensor error 2 P2 Pipe TH2 sensor error 3 E6 E7 Indoor outdoor unit communication error 4 P4 Dr...

Page 14: ...sible due to system start up Correct operation Connector for the outdoor unit s protection device is not connected Reverse or open phase wiring for the outdoor unit s power terminal block L1 L2 L3 Inc...

Page 15: ...heck resistance value of thermistor For characteristics refer to P1 above 2 Check contact failure of connector CN44 on the indoor controller board Refer to 9 7 TEST POINT DIAGRAM Turn the power on and...

Page 16: ...or fan motor Fan motor is defective Indoor controller board is defec tive 5 Defective outdoor fan control 6 Overcharge of refrigerant 7 Defective refrigerant circuit clogs 8 Bypass circuit of outdoor...

Page 17: ...Set one of the remote controllers main if there is no problem with the action above 3 Check wiring of remote controller Total wiring length max 500m Do not use cable 3 or more The number of connecting...

Page 18: ...ler circuit board to transmit signals Indoor controller board Abnormal if data cannot be read normally from the nonvolatile memory of the indoor controller board 1 Defective indoor controller board 1...

Page 19: ...ouble 2 Drain defective Drain pump clogging Drain pipe clogging 3 Open circuit of float switch 4 Contact failure of float switch connector 5 Dew condensation on float switch Drain water descends along...

Page 20: ...al block S1 and S2 When 220 240 V AC is not detected check indoor outdoor unit connecting wire for miswiring When 220 240 V AC is detected check 4 below 4 Check the fuse on indoor controller board Che...

Page 21: ...k the connection of remote controller wires in the case of twin triple indoor unit system When 2 or more indoor units are wired in one refrigerant system connect remote controller wires to one of thos...

Page 22: ...unit operates as follows 1 Indoor fan is running at high speed 2 Drain pump is operating Note on the wireless remote control When the remote control does not function it is possible to activate Emerg...

Page 23: ...llow 1 Brown Orange 3 Green 5 Connect pin No M Refer to 9 6 2 DC Fan motor fan motor indoor controller circuit board 0 10 20 30 40 50 20 10 0 10 20 30 40 50 Thermistor for lower temperature Temperatur...

Page 24: ...VDC 310 340 V DC TEST POINT 2 VCC between 4 and 3 of the fan connector VCC 15 V DC Wiring recovery Replace the indoor controller board Replace the fan motor Replace the indoor controller board Replac...

Page 25: ...re J41 J42 Pair No setting for wireless remote controller CN01 Connect to the Terminal block TB4 1 3 220 240 V AC LED1 Power supply I B LED2 Power supply R B LED3 Transmission Indoor outdodr CN3C Tran...

Page 26: ...The pair number settings of the wireless remote controller and indoor control PCB J41 J42 are given in the table on the left in the table indicates the jumper wire is disco nnected Marks in the table...

Page 27: ...d Back up function Outline of functions Main and sub unit operate alternately according to the interval of rotation setting Main and sub unit should be set by refrigerant address Outdoor DIP switch se...

Page 28: ...itoring the request code of current setting Setting contents Rotation ON Alternating interval 28days and back up function Rotation ON Alternating interval 14days and back up function Rotation ON Alter...

Page 29: ...en D when Maintenance monitor is activated The display D now allows you to set a request code No 4 Press the TEMP and buttons 4 to select the desired refrigerant address 5 Press the CLOCK and buttons...

Page 30: ...tors on the indoor controller board See Photo 3 4 Remove the switch board holder and open the cover 5 Pull out the indoor controller board toward you then remove the indoor controller board and switch...

Page 31: ...r to 1 2 Remove the electrical box covers Refer to 2 3 Disconnect the vane motor connector CN151 on the indoor controller board 4 Pull out the drain hose from the nozzle assembly and remove nozzle ass...

Page 32: ...eat exchanger See Photo 9 10 Lift the heat exchanger and pull out the line flow fan to the lower left Photo 7 7 Removing the pipe temperature thermistor liquid TH2 and cond eva temperature thermistor...

Page 33: ...f the heat exchanger See Photo 9 7 Remove the heat exchanger 9 Removing the room temperature thermistor 1 Remove the panel and corner box Refer to 1 2 Remove the electrical box covers 3 Remove the roo...

Page 34: ...2009 MITSUBISHI ELECTRIC CORPORATION Distributed in Jul 2014 No OCH452 REVISED EDITION B Distributed in May 2011 No OCH452 REVISED EDITION A Distributed in Feb 2009 No OCH452 PDF 6 Made in Japan New...

Reviews: