background image

17

Check code

Abnormal point and detection method 

Cause

Countermeasure

P9

Pipe temperature thermistor / 

Condenser-Evaporator (TH5)

1

 The unit is in 3-minute resume protec-

tion mode if short/open of thermistor is 

detected. Abnormal if the unit does not 

get back to normal within 3 minutes. (The 

unit returns to normal operation, if it has 

been reset normally.)

2

 Constantly detected during cooling, 

drying, and heating operation (except 

defrosting)

  Short: 90

:

 or more

  Open: −40

:

 or less

1

 Defective thermistor 

characteristics

2

 Contact failure of connector 

(CN44) on the indoor controller 

board (Insert failure)

3

 Breaking of wire or contact 

failure of thermistor wiring

4

 Temperature of thermistor is 

90

:

 or more or −40

:

 or less 

caused by defective refrigerant 

circuit.

5

 Defective indoor controller 

board

1

Check resistance value of thermistor.

 

For characteristics, refer to (P1) above.

2

 Check contact failure of connector (CN44) on 

the indoor controller board. 

  Refer to

 "9-7 TEST POINT DIAGRAM"

.

  Turn the power on and check restart after 

inserting connector again.

4

 Operate in test run mode and check pipe 

<condenser / evaporator> temperature with 

outdoor controller circuit board.  If pipe 

<condenser / evaporator> temperature is 

extremely low (in cooling mode) or high (in 

heating mode), refrigerant circuit may have 

defect.

5

 Operate in test run mode and check pipe 

<condenser / evaporator> temperature 

with outdoor control circuit board.  If there 

is extreme difference with actual pipe 

<condenser / evaporator> temperature, 

replace indoor controller board.

  There is no abnormality if none of the above 

comes within the unit.

  Turn  the power off and on again to operate.

E0

or

E4

Remote controller transmission error(E0)/

signal receiving error(E4)

1

 Abnormal if main or sub remote con-

troller cannot receive any transmission 

normally from indoor unit of refrigerant 

address “0” for 3 minutes.

  (Check code : E0)

2

 Abnormal if sub remote controller could 

not receive any signal for 2 minutes. 

(Check code: E0) 

1

 Abnormal if indoor controller board can 

not receive any data normally from 

remote controller board or from other 

indoor controller board for 3 minutes. 

(Check code: E4)

2

 Indoor controller board cannot receive 

any signal from remote controller for 2 

minutes. (Check code: E4)

1

 Check disconnection or looseness of indoor 

unit or transmission wire of remote controller.

2

 Set one of the remote controllers “main” if 

there is no problem with the action above.

3

 Check wiring of remote controller.

• Total wiring length: max. 500m

  (Do not use cable × 3 or more.)

• The number of connecting indoor units: 

max. 16 units

• The number of connecting remote controller:

 

max. 2 units

When it is not the above-mentioned problem of 

1

3

4

 Diagnose remote controllers.

a) When “RC OK” is displayed,

Remote controllers have no problem. 

Turn the power off, and on again to check. 

If abnormality generates again, replace 

indoor controller board.

b) When “RC NG” is displayed,

Replace remote controller.

c) When “RC E3” or “ERC 00-66” is dis

-

played, noise may be causing abnormality.

 Note: 

  If the unit is not normal after replacing indoor 

controller board in group control, indoor con

-

troller board of address “0” may be abnormal.

1

 Contact failure at transmission 

wire of remote controller

2

 All remote controllers are set 

as “sub” remote controller. 

In this case, E0 is displayed 

on remote controller, and E4 

is displayed at LED (LED1, 

LED2) on the outdoor controller 

circuit board.

3

 Miswiring of remote controller

4

 Defective transmitting receiving 

circuit of remote controller

5

 Defective transmitting receiving 

circuit of indoor controller board 

of refrigerant addresses “0”.

6

 Noise has entered into the 

transmission wire of remote 

controller.

In case of checking pipe temperature 

with outdoor controller circuit board, 

be sure to connect A-control service 

tool (PAC-SK52ST).

(

)

PL

 Abnormal refrigerant circuit

  During Cooling, Dry, or Auto Cooling 

operation, the following conditions are 

regarded as failures when detected for 1 

second.

a) The compressor continues to run for 30 

or more seconds.

b) The liquid pipe temperature or the 

condense/evaporator temperature is 

75°C or more.

These detected errors will not be 

cancelled until the power source is 

reset.

 Abnormal operation of 4-way 

valve

 Disconnection of or leakage in 

refrigerant pipes

 Air into refrigerant piping

 Abnormal operation (no 

rotation) of indoor fan

  ·  Defective fan motor.

  ·  Defective indoor control 

board. 

 Defective refrigerant circuit 

(clogging)

 When this error occurs, be sure to 

replace the 4-way valve.

 Check refrigerant pipes for disconnection or 

leakage.

 After the recovery of refrigerant, vacuum 

dry the whole refrigerant circuit.

Refer to "9-6-2. DC Fan motor (fan motor/ 

indoor controller board".

 Check refrigerant circuit for operation.

 

 To avoid entry of moisture or air into 

refrigerant circuit which could cause 

abnormal high pressure, purge air in 

refrigerant circuit or replace refrigerant.

OCH452B

Summary of Contents for PKA-RP100KALR1.TH

Page 1: ...N OFF TEMP PARTS CATALOG OCB452 INDOOR UNIT PKA RP60KAL TH PKA RP60KAL TH ER PKA RP60KALR1 TH PKA RP60KALR1 TH ER PKA RP71KAL TH PKA RP71KAL TH ER PKA RP71KALR1 TH PKA RP71KALR1 TH ER PKA RP100KAL TH...

Page 2: ...ZRP60 71VHA PUHZ RP35 50 60 71VHA4 PUHZ RP100 125 140VKA PUHZ RP100 125 140 200 250YKA PU H P71 100VHA PU H P71 100 125 140YHA PUHZ HRP100VHA2 PUHZ HRP100YHA2 PUHZ ZRP100VKA2 UK PUHZ ZRP100YKA2 UK PUH...

Page 3: ...com pressor Do not use a charging cylinder If a charging cylinder is used the composition of refrigera nt will change and the efficiency will be lowered Flare tool Electronic refrigerant charging scal...

Page 4: ...rse flow check Attach on vacuum pump 6 Refrigerant charge base 7 Refrigerant cylinder Only for R410A Top of cylinder Pink Cylinder with syphon 8 Refrigerant recovery equipment 1 Cautions for service 1...

Page 5: ...isplays whether timer is on or off Buttons used to set the hour and minute of the current time and timer settings h and min buttons display display FAN SPEED display indicates which fan speed has been...

Page 6: ...46 kW A kW K min CFM Pa mmAq kW dB mm in mm in mm in mm in kg lb Mode Power supply phase cycle voltage Input Running current External finish Panel Heat exchanger Fan Fan drive o No Fan motor output A...

Page 7: ...20 230 240V 50Hz 10 0 15 0 20 0 25 0 30 0 35 0 40 0 45 0 50 0 55 0 60 0 65 0 70 0 63 125 250 500 1k 2k 4k 8k NC 60 NC 50 Octave band pressure level dB 0dB 20 Pa Approximate minimum audible limit on co...

Page 8: ...T STAND BY lamp Receiver Knockout hole for right piping Mount board Right side 444 Gas pipe 482 Liquid pipe 585 Drain hose Filter hook Under side Vane auto Knockout hole for lower piping Louver manual...

Page 9: ...te controller transmission line TB6 TH2 SW1 TH5 SW2 SWE LEGEND TO OUTDOOR UNIT 5 3 1 3 1 CN01 BLK ORN YLW BLU RED GRN YLW I B w1 Fig 1 I B TB2 POWER SUPPLY 1PHASE 230V 50Hz ORN ORN YLW BRN TB4 INDOOR...

Page 10: ...low in heating Strainer 50 Strainer 50 Heat exchanger Refrigerant GAS pipe connection Flare Refrigerant LIQUID pipe connection Flare REFRIGERANT SYSTEM DIAGRAM 8 PKA RP60KAL TH PKA RP71KAL TH PKA RP10...

Page 11: ...ording to 9 4 TROUBLESHOOTING BY INFERIOR PHENOMENA The trouble is not reoccurring Logged Not logged 1Consider the temporary defects such as the work of protection devices in the refrigerant circuit i...

Page 12: ...s cancelled Procedure 1 Press the CHECK button twice 2 Press the temperature buttons 3 Point the remote controller at the sensor on the indoor unit and press the HOUR button 4 Point the remote control...

Page 13: ...Number of times Wireless remote controller Wired remote controller 1 P1 Intake sensor error P9 Pipe TH5 sensor error 2 P2 Pipe TH2 sensor error 3 E6 E7 Indoor outdoor unit communication error 4 P4 Dr...

Page 14: ...sible due to system start up Correct operation Connector for the outdoor unit s protection device is not connected Reverse or open phase wiring for the outdoor unit s power terminal block L1 L2 L3 Inc...

Page 15: ...heck resistance value of thermistor For characteristics refer to P1 above 2 Check contact failure of connector CN44 on the indoor controller board Refer to 9 7 TEST POINT DIAGRAM Turn the power on and...

Page 16: ...or fan motor Fan motor is defective Indoor controller board is defec tive 5 Defective outdoor fan control 6 Overcharge of refrigerant 7 Defective refrigerant circuit clogs 8 Bypass circuit of outdoor...

Page 17: ...Set one of the remote controllers main if there is no problem with the action above 3 Check wiring of remote controller Total wiring length max 500m Do not use cable 3 or more The number of connecting...

Page 18: ...ler circuit board to transmit signals Indoor controller board Abnormal if data cannot be read normally from the nonvolatile memory of the indoor controller board 1 Defective indoor controller board 1...

Page 19: ...ouble 2 Drain defective Drain pump clogging Drain pipe clogging 3 Open circuit of float switch 4 Contact failure of float switch connector 5 Dew condensation on float switch Drain water descends along...

Page 20: ...al block S1 and S2 When 220 240 V AC is not detected check indoor outdoor unit connecting wire for miswiring When 220 240 V AC is detected check 4 below 4 Check the fuse on indoor controller board Che...

Page 21: ...k the connection of remote controller wires in the case of twin triple indoor unit system When 2 or more indoor units are wired in one refrigerant system connect remote controller wires to one of thos...

Page 22: ...unit operates as follows 1 Indoor fan is running at high speed 2 Drain pump is operating Note on the wireless remote control When the remote control does not function it is possible to activate Emerg...

Page 23: ...llow 1 Brown Orange 3 Green 5 Connect pin No M Refer to 9 6 2 DC Fan motor fan motor indoor controller circuit board 0 10 20 30 40 50 20 10 0 10 20 30 40 50 Thermistor for lower temperature Temperatur...

Page 24: ...VDC 310 340 V DC TEST POINT 2 VCC between 4 and 3 of the fan connector VCC 15 V DC Wiring recovery Replace the indoor controller board Replace the fan motor Replace the indoor controller board Replac...

Page 25: ...re J41 J42 Pair No setting for wireless remote controller CN01 Connect to the Terminal block TB4 1 3 220 240 V AC LED1 Power supply I B LED2 Power supply R B LED3 Transmission Indoor outdodr CN3C Tran...

Page 26: ...The pair number settings of the wireless remote controller and indoor control PCB J41 J42 are given in the table on the left in the table indicates the jumper wire is disco nnected Marks in the table...

Page 27: ...d Back up function Outline of functions Main and sub unit operate alternately according to the interval of rotation setting Main and sub unit should be set by refrigerant address Outdoor DIP switch se...

Page 28: ...itoring the request code of current setting Setting contents Rotation ON Alternating interval 28days and back up function Rotation ON Alternating interval 14days and back up function Rotation ON Alter...

Page 29: ...en D when Maintenance monitor is activated The display D now allows you to set a request code No 4 Press the TEMP and buttons 4 to select the desired refrigerant address 5 Press the CLOCK and buttons...

Page 30: ...tors on the indoor controller board See Photo 3 4 Remove the switch board holder and open the cover 5 Pull out the indoor controller board toward you then remove the indoor controller board and switch...

Page 31: ...r to 1 2 Remove the electrical box covers Refer to 2 3 Disconnect the vane motor connector CN151 on the indoor controller board 4 Pull out the drain hose from the nozzle assembly and remove nozzle ass...

Page 32: ...eat exchanger See Photo 9 10 Lift the heat exchanger and pull out the line flow fan to the lower left Photo 7 7 Removing the pipe temperature thermistor liquid TH2 and cond eva temperature thermistor...

Page 33: ...f the heat exchanger See Photo 9 7 Remove the heat exchanger 9 Removing the room temperature thermistor 1 Remove the panel and corner box Refer to 1 2 Remove the electrical box covers 3 Remove the roo...

Page 34: ...2009 MITSUBISHI ELECTRIC CORPORATION Distributed in Jul 2014 No OCH452 REVISED EDITION B Distributed in May 2011 No OCH452 REVISED EDITION A Distributed in Feb 2009 No OCH452 PDF 6 Made in Japan New...

Reviews: