background image

6

4. Installing the outdoor unit

(mm)

• Be sure to install the unit in a sturdy, level surface to prevent rattling noises during

operation. (Fig. 4-1)

<Foundation specifications>

Foundation bolt

M10 (3/8")

Thickness of concrete

120 mm

Length of bolt

70 mm

Weight-bearing capacity

320 kg

• Make sure that the length of the foundation bolt is within 30 mm of the bottom

surface of the base.

• Secure the base of the unit firmly with four-M10 foundation bolts in sturdy locations.

Installing the outdoor unit

• Do not block the vent. If the vent is blocked, operation will be hindered and break-

down may result.

• In addition to the unit base, use the installation holes on the back of the unit to

attach wires, etc., if necessary to install the unit. Use self-tapping screws (ø5 

×

 15

mm or more) and install on site.

 Warning:

• The unit must be securely installed on a structure that can sustain its weight.

If the unit is mounted on an unstable structure, it may fall down and cause
damage or injuries.

• The unit must be installed according to the instructions in order to minimize

the risk of damage from earthquakes, typhoons, or strong winds. An incor-
rectly installed unit may fall down and cause damage or injuries.

Fig. 4-1

A

M10 (3/8") bolt

B

Base

C

As long as possible.

D

Vent

5. Installing the refrigerant piping

5.1. Precautions for devices that use R410A refrigerant

• Refer to page 3 for precautions not included below on using air conditioners

with R410A refrigerant.

• Use ester oil, ether oil, alkylbenzene oil (small amount) as the refrigeration oil

applied to the flared sections.

• Use C1220 copper phosphorus, for copper and copper alloy seamless pipes,

to connect the refrigerant pipes. Use refrigerant pipes with the thicknesses
specified in the table to the below. Make sure the insides of the pipes are
clean and do not contain any harmful contaminants such as sulfuric com-
pounds, oxidants, debris, or dust.

 Warning:

When installing or moving the air conditioner, use only the specified refriger-
ant (R410A) to charge the refrigerant lines. Do not mix it with any other refriger-
ant and do not allow air to remain in the lines. Air enclosed in the lines can
cause pressure peaks resulting in a rupture and other hazards.

ø6.35, ø9.52, ø12.7

Thickness 0.8 mm

ø15.88

Thickness 1.0 mm

• Do not use pipes thinner than those specified above.

5.2. Pipe length and height difference (Fig. 5-1)

Flared connections

• This unit has flared connections on each indoor unit and branch box and outdoor

unit sides.

• Remove the valve cover of the outdoor unit, then connect the pipe.
• Refrigerant pipes are used to connect the branch box and outdoor unit.

Fig. 5-1

Total piping length

b1+b2+a1+a2+a3+a4+a5+a6+a7+a8 

 115 m

Farthest piping length (L)

b2+a8 

 70 m (b2 

 55 m, a8 

 15 m)

Piping length between outdoor unit and branch boxes

b1+b2 

 55 m

Farthest piping length after branch box (l)

a8 

 15 m

Total piping length between branch boxes and indoor units

a1+a2+a3+a4+a5+a6+a7+a8 

 60 m

In indoor/outdoor section (H)*1

 30 m (In case of outdoor unit is set higher than indoor unit)

 20 m (In case of outdoor unit is set lower than indoor unit)

In branch box/indoor unit section (h1)

h1 + h2 

 15 m

In each branch unit (h2)

h2 

 15 m

In each indoor unit (h3)

h3 

 12 m

| b1+a1 |, | b1+a2 |, | b1+a3 |, | b1+a4 |, | b1+a5 |, | b2+a6 |, | b2+a7 |, | b2+a8 | 

 15

Permissible

length

(one-way)

A

B

C

B

C

C

C

C

C

C

C

L

I

h2

b2

b1

a6

a5

a4

a3

a2

h3

h1

H

a1

a7 a8

A

Outdoor unit

B

Branch box

C

Indoor unit

B

Max.

 30

Permissible

height difference

(one-way)

Number of bends

*1 Branch box should be placed within the level between the outdoor unit and indoor units.

A

C

D

600

600

Min. 360

175

175

Min. 10

950

25

330

370

Summary of Contents for MXZ-8A140VA

Page 1: ......

Page 2: ...rrectly and dust and moisture enter the unit electric shock or fire may result When installing or moving the air conditioner use only the specified refriger ant R410A to charge the refrigerant lines Do not mix it with any other refrig erant and do not allow air to remain in the lines Air enclosed in the lines can cause pressure peaks resulting in a rupture and other hazards Use only accessories au...

Page 3: ...es that carried R22 refriger ant Replace the existing flare nuts and flare the flared sections again Do not use thin pipes Refer to page 6 Store the pipes to be used during installation indoors and keep both ends of the pipes sealed until just before brazing Leave elbow joints etc in their packaging If dust debris or moisture enters the refrigerant lines oil dete rioration or compressor breakdown ...

Page 4: ...d Refer to the table below for possible 2 8 room indoor unit combinations Verification The rated capacity should be determined by observing the table below The unit s quantities are limited in 2 to 8 units For the next step make sure that the total rated capacity selected will stay in a range of 4 4 18 5 kW Example MSZ 60 6 0 SEZ 35 3 5 SLZ 35 3 5 Total rated capacity SEZ 25 2 5 18 0 18 5 kW SLZ 2...

Page 5: ...r and above only Fig 3 12 No more than three units must be installed side by side In addition leave space as shown Do not install the optional air outlet guides for upward airflow 3 Obstacles at front only Fig 3 13 When using an optional air outlet guide the clearance is 1000 mm or more 4 Obstacles at front and rear only Fig 3 14 When using an optional air outlet guide the clearance is 1000 mm or ...

Page 6: ... thicknesses specified in the table to the below Make sure the insides of the pipes are clean and do not contain any harmful contaminants such as sulfuric com pounds oxidants debris or dust Warning When installing or moving the air conditioner use only the specified refriger ant R410A to charge the refrigerant lines Do not mix it with any other refriger ant and do not allow air to remain in the li...

Page 7: ...ox Flare connection employed No brazing In case of using 2 branch boxes Branch box 1 2 branches pipe joint optional parts Branch box 2 Conversion formula 1 4 F ø6 35 3 8 F ø9 52 1 2 F ø12 7 5 8 F ø15 88 3 4 F ø19 05 5 3 Addition of refrigerant Additional charging is not necessary for this unit if the total pipe length b1 b2 a1 a2 a3 a4 a5 a6 a7 a8 does not exceed 40 m If the total pipe length exce...

Page 8: ... series indoor unit Indoor unit kW 35 50 60 71 type Pipe size Liquid ø6 35 ø6 35 ø9 52 ø9 52 ømm Gas ø12 7 ø12 7 ø15 88 ø15 88 When using 35 50 type indoor unit of P series use the flare nut attached to the indoor unit Do not use the flare nut in the indoor unit accessory If it is used a gas leakage or even a pipe extraction may occur When bending the pipes be careful not to break them Bend radii ...

Page 9: ...iping side I Direction the refrigerant flows in J Wrench hole K Operation section 5 8 Airtight test and evacuation 1 Airtight test Fig 5 9 Airtight test should be made by pressurizing nitrogen gas For the test method refer to the following figure 1 Connecting the testing tool Make a test with the stop valve closed Be also sure to pressurize both liquid or high pressure pipe and gas or low pressure...

Page 10: ...C Valve D 3 way joint E Vacuum pump F System analyzer G Lo knob LO HI G H N D C E C A B M L K J I F Fig 5 10 H Hi knob I To branch box J Outdoor unit K Stop valve L Liquid pipe or high pressure pipe M Gas pipe or low pressure pipe N Service port 2 Evacuation Fig 5 10 Evacuation should be made from the service port provided on the outdoor unit s stop valve to the vacuum pump commonly used for both ...

Page 11: ...ller 3 2 Group operation between different refrigerant systems 3 3 Connection of M NET adapter to outdoor unit Master controller G 50 etc Power supply unit 3 branch type 3 branch type 3 branch type 3 branch type 7 1 Outdoor unit Fig 7 1 1 Remove the service panel 2 Wire the cables referring to the Fig 7 1 A Earth terminal B Terminal block C Clamp D Service panel E Wire the cables so that they do n...

Page 12: ...s E Power supply single phase AC220 230 240 V 50 Hz AC220 V 60 Hz Max Permissive System Impedance 0 22 Ω Note 1 Power supply input Outdoor unit only Connect the lines C D in accordance with the terminal block names to ensure correct polarity When using twisted wire for the wiring the use of round terminal is required 1 A breaker with at least 3 mm contact separation in each pole shall be provided ...

Page 13: ...indoor branch box connecting cables directly to the units no intermediate connections Intermediate connections can lead to communication errors if water enters the cables and causes insufficient insulation to ground or a poor electrical contact at the intermediate connection point If an intermediate connection is necessary be sure to take measures to prevent water from entering the cables 7 Electr...

Page 14: ...ce is less than 1 MΩ Insulation resistance After installation or after the power source to the unit has been cut for an extended period the insulation resistance will drop below 1 MΩ due to refrigerant accumulat ing in the compressor This is not a malfunction Perform the following procedures 1 Remove the wires from the compressor and measure the insulation resistance of the compressor 2 If the ins...

Page 15: ...upply F Procure locally G Max 10m CN51 X 5 4 3 A C D 5 E 1 B G Y X Y L1 L2 F L1 Error display lamp L2 Compressor operation lamp X Y Relay Coil standard of 0 9W or less for DC 12V X Y Relay DC1mA 9 4 Auto change over Operation mode locking func tion by external signal CN3S A Remote control panel B Relay circuit C External input adapter PAC SC36NA D Outdoor unit control board E Relay power supply F ...

Page 16: ...73 23 EEC Electromagnetic Compatibility Directive 89 336 EEC This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Printed in Japan BG79U438H04 The product at hand is based on the following EU regulations ...

Reviews: