1-5. INSTALLATION DIAGRAM

Units should be installed by licensed contractor according to local code requirements.

ACCESSORIES 

Check the following parts before installation.

(1) Drain socket

1

(2) Drain cap

5

PARTS TO BE PROVIDED AT YOUR SITE

(A) Power supply cord*

1

(B) Indoor/outdoor unit connecting wire

*

1

(C) Extension pipe

1

(D) Wall hole cover

1

(E) Piping tape

1

(F)

Extension drain hose 

(or soft PVC hose, 15 mm inner 

diameter or hard PVC pipe VP16)

1

(G)

Refrigeration oil

Little 

amount

(H) Putty

1

(I) Pipe fixing band

2 to 7

(J) Fixing screw for (I)

2 to 7

(K) Wall hole sleeve

1

(L)

Soft PVC hose, 15 mm inner 

diameter or hard PVC pipe VP16 

for drain socket (1)

1

Note:

*Place indoor/outdoor unit connecting wire (B) and 

power supply cord (A) at least 1 m away from the 

TV antenna wire.

The “Q’ty” for (B) to (K) in the above table is quantity 

to be used per indoor unit.

More than 

100 mm

Open as a rule

More than 500 mm 

if the front and both 

sides are open

More than 100 mm 

More than 200 mm if there are 

obstacles to both sides

Open as a rule

More than 500 mm if the back, 

both sides and top are open

More than 350 mm

Outdoor unit installation

Air inlet

Air outlet

Air inlet

950 mm

600 mm

175 

mm

2-U-shape notched holes

(Base bolt M10)

330

 mm

2 - 12 mm × 36 mm 

 

oval holes (Base bolt M10)

370

 mm

417

 mm

After  the  leak  test,  apply  insulat

-

ing material tightly so that there 

is no gap.

When the piping is to be attached to 

a wall containing metals (tin plated) 

or metal netting, use a chemically 

treated  wooden  piece  20  mm  or 

thicker  between  the  wall  and  the 

piping or wrap 7 to 8 turns of insula

-

tion vinyl tape around the piping.

To  use  existing  piping,  perform 

COOL  operation  for  30  minutes 

and  pump  down  before  removing 

the old air conditioner. Remake flare 

according to the dimension for new 

refrigerant.

1-6. DRAIN PIPING FOR OUTDOOR UNIT 

1)  Perform the drain piping work only when draining from one place.

2)  Provide drain piping before indoor and outdoor piping connection. 

3)  Attach the drain socket to one of the several drain holes.

  Fix the drain socket into the drain hole of the base using the catches to secure it 

in place.

4)  Connect the soft PVC hose I.D.15 mm as shown in the illustration.

5)  Make sure to provide drain piping with a downhill grade for easy drain flow.

6)  Glue the drain caps to close all the other unnecessary holes with the glue (Prepare 

in the field).

Note:

Apply the glue securely, as the glue (Prepare in the field) will work as seal to prevent 

water from leaking.

Use the adhesive for the rubber and metal.

Attention

The outdoor unit is provided with several holes for drainage at the bottom to make 

drainage easier. 

The drain socket is used to close the unnecessary holes and centralize the drainage 

when using the drain tube at the installation place.

Do not to use the drain socket in cold region. The drain tube can be frozen.

(1) Drain socket

(2) Drain cap

(L) Soft PVC hose

IMPORTANT NOTES

To comply with the requirements of Australian standard AS/NZS 3000 electrical installations 

(wiring  rules),  the  electrical  wiring  required  between  the  indoor  and  outdoor  units  must  be 

installed by a licenced electrical contractor.

WG79A696H02_en.indd   3

2016/04/21   14:46:36

Summary of Contents for MXZ-4E80VAD

Page 1: ...ual For INSTALLER This manual only describes the installation of outdoor unit When installing the indoor unit refer to the installation manual of indoor unit Split type Air Conditioner MXZ 4E80VAD MXZ 5E100VAD English ...

Page 2: ...Check that the refrigerant gas does not leak after installation has been completed If refrigerant gas leaks indoors and comes into contact with the flame of a fan heater space heater stove etc harmful substances will be generated n Use appropriate tools and piping materials for installation The pressure of R410A is 1 6 times more than R22 Not using appropriate tools or materials and incomplete ins...

Page 3: ...ow or there is a possibility of becoming short cycle install an outlet guide and make sure there is enough space behind of the unit When installing two or more units do not install the units in front or behind each other 100 or more 200 or more 350 or more 500 or more 500 or more Unit mm 5 Obstacles in front behind and on side s 4 Obstacles in front and behind The unit can be used by at taching an...

Page 4: ...ically treated wooden piece 20 mm or thicker between the wall and the piping or wrap 7 to 8 turns of insula tion vinyl tape around the piping To use existing piping perform COOL operation for 30 minutes and pump down before removing the old air conditioner Remake flare according to the dimension for new refrigerant 1 6 DRAIN PIPING FOR OUTDOOR UNIT 1 Perform the drain piping work only when drainin...

Page 5: ... tighten the terminal screws to prevent them from loosening After tightening pull the wires lightly to confirm that they do not move 4 Perform 2 and 3 for each indoor unit 5 Connect power supply cord A 6 Fix indoor outdoor unit connecting wire B and power supply cord A with the cable clamps Route the cables or wires so as not to deform the service panel Otherwise rainwater may enter the outdoor un...

Page 6: ...revent burrs from dropping in the pipe 3 Remove flare nuts attached to indoor and outdoor units then put them on pipe having completed burr removal Not possible to put them on after flaring work 4 Flaring work Fig 4 5 Firmly hold copper pipe in the dimension shown in the table Select A mm from the table according to the tool selected 5 Check Compare the flared work with Fig 6 If flare is noted to ...

Page 7: ... service port to obtain the initial status 10 Leak test Stop valve for GAS Gauge mani fold valve for R410A Compound pressure gauge for R410A 0 101MPa 760 mmHg Handle Low Handle High Vacuum pump for R410A Charge hose for R410A Close Open Hexagonal wrench 4 to 5 turns Stop valve for LIQUID Pressure gauge for R410A Precautions when us ing the control valve When attaching the control valve to the serv...

Page 8: ...r unit During detection the indoor unit automatically stops operation This is not a malfunction Procedure Press the piping wiring correction switch SW871 1 minute or more after turning on the power supply Correction completes in 10 to 20 minutes When the correction is completed its result is shown by LED indication Details are described in the following table To cancel this function during its ope...

Page 9: ......

Page 10: ......

Page 11: ......

Page 12: ...WG79A696H02 HEAD OFFICE TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN ...

Reviews: