background image

9

Indoor unit model

PKA-RP·HAL

Indoor unit power supply

Indoor unit input capacity 

*1

Main power switch (Breaker)

– 

Wiring 

Wire

 No.

 ×

 size

  

(mm

2

)

Indoor unit power supply

Indoor unit earth

1 × Min. 1.5

Indoor unit-Outdoor unit 

*2

3 × 1.5 (Polar)

Indoor unit-Outdoor unit earth 

*2

1 × Min. 1.5

Wired remote controller (option) Indoor unit 

*3

2 × Min. 0.3

Circuit

  

rating

Indoor unit L-N 

*4

Indoor unit-Outdoor unit S1-S2 

*4

AC 230 V

Indoor unit-Outdoor unit S2-S3 

*4

DC 24 V

Wired remote controller (option) Indoor unit 

*4

DC 12 V

*1. A breaker with at least 3 mm contact separation in each pole shall be provided. Use non-fuse breaker (NF) or earth leakage breaker (NV).
*2. <For 25-140 outdoor unit application>
  Max. 45 m
  If 2.5 mm

2

 used, Max. 50 m

  If 2.5 mm

2

 used and S3 separated, Max. 80 m

  For PUHZ-RP100/125/140 YHA application, use shield wires. The shield part must be grounded with the indoor unit OR the outdoor unit, NOT with both.
  <For 200/250 outdoor unit application>
  Max. 18 m
  If 2.5 mm

2

 used, Max. 30 m

  If 4 mm

2

 used and S3 separated, Max. 50 m

  If 6 mm

2

 used and S3 separated, Max. 80 m

*3. Max. 500 m
*4. The figures are NOT always against the ground.
  S3 terminal has DC 24 V against S2 terminal. However between S3 and S1, these terminals are not electrically insulataed by the transformer or other device.

Notes:  1.  Wiring size must comply with the applicable local and national code.

 

2.  Power supply cords and Indoor unit/Outdoor unit connecting cords shall not be lighter than polychloroprene sheathed flexible cord. (Design 245 IEC 

57)

 

3.  Install an earth longer than other cords.

6.  Electrical work

6.1.2.  Separate indoor unit/outdoor unit power supplies (For PUHZ application only)

The following connection patterns are available.

The outdoor unit power supply patterns vary on models.

*  The optional wiring replacement kit is required.

S1
S2

L
N

1
2

L

N

S1
S2
S3

S3

A

C

B

D

J

E

B

C

F

G

H

S1
S2

L
N

1
2

L

N

S1
S2
S3

L

N

S1
S2
S3

L

N

S1
S2
S3

L

N

S1
S2
S3

S3

A

B

C

D

E

J

B

C

F

H

G

G

G

G

H

H

H

K

K

K

*  Affix a label B that is included with the manuals near each wiring diagram for the indoor and outdoor units.

Outdoor unit power supply

Earth leakage breaker

Wiring circuit breaker or isolating switch

Outdoor unit

Indoor/outdoor unit connecting cords

Wired remote controller (option)

Indoor unit

Option

Indoor unit power supply

*  The optional wiring replacement kits are required.

Simultaneous twin/triple/four system

*  Affix a label B that is included with the manuals near each wiring diagram for the indoor and outdoor units.

Outdoor unit power supply

Earth leakage breaker

Wiring circuit breaker or isolating switch

Outdoor unit

Indoor/outdoor unit connecting cords

Wired remote controller (option)

Indoor unit

Option

Indoor unit power supply

Indoor unit earth

1:1 System

RG79D479H02_en.indd   9

2012/10/09 (火)   午前 11:37:55

Summary of Contents for Mr.Slim PKA-RP35HAL

Page 1: ...begint MANUALE DI INSTALLAZIONE Per un uso sicuro e corretto prima di installare il condizionatore d aria leggere attentamente il presente manuale ed il manuale d installazione dell unit esterna MANU...

Page 2: ...changes or dripping water When the room humidity exceeds 80 or when the drainpipe is clogged water may drip from the indoor unit Do not install the indoor unit where such dripping can cause damage Whe...

Page 3: ...am to the left The hole should incline so that the outside opening is lower than the inside opening Insert a sleeve with a 75 mm diameter and purchased locally through the hole A Sleeve B Hole C Indoo...

Page 4: ...rking on the mount board as a reference when adjusting the length of the embedded cooling pipe During construction give the length of the extruding pipes etc some leeway A Mount board 1 B Reference ma...

Page 5: ...ve the indoor unit to the left and right and verify that the indoor unit is hung securely 5 Fasten by pushing the bottom part of the indoor unit onto the mount board 1 Fig 3 10 Check that the knobs on...

Page 6: ...6 35 17 14 18 12 7 28 49 61 PKA RP HAL Fig 4 3 B A 4 2 Indoor unit Refrigerant and Drainage Piping Sizes Item Model PKA RP35 RP50HAL Refrigerant piping Liquid OD 6 35 1 4 Gas OD 12 7 1 2 Drainage pip...

Page 7: ...r H Drainage ditch I 5 cm or less between the end of drain pipe and the ground J Drain hose K Soft PVC hose Inside diameter 15 mm or Hard PVC pipe VP 16 Bond with PVC type adhesive Preparing left and...

Page 8: ...te control cord J Indoor outdoor connection cord K Hook L Ground wire connection portion Warning Never splice the power cable or the indoor outdoor connection cable otherwise it may result in a smoke...

Page 9: ...ize must comply with the applicable local and national code 2 Power supply cords and Indoor unit Outdoor unit connecting cords shall not be lighter than polychloroprene sheathed flexible cord Design 2...

Page 10: ...door unit DIP switch settings when using separate indoor unit outdoor unit power supplies only ON OFF 1 2 SW8 3 There are three types of labels labels A B and C Affix the appropriate labels to the uni...

Page 11: ...he min button twice continuously Pair No 0 blinks 3 Press the temp button to set the pair number you want to set 4 Press the SET button with something sharp at the end Set pair number is lighted for t...

Page 12: ...ly 6 Complete function selection Direct the wireless remote controller toward the sensor of the indoor unit and press the button E Note Whenever changes are made to the function settings after install...

Page 13: ...mode then check whether warm air is blown out from the unit 5 Press the FAN button and check whether fan speed changes 6 Press the VANE button and check whether the auto vane operates properly 7 Press...

Page 14: ...U6 Compressor overcurrent interruption Abnormal of power module 10 U7 Abnormality of super heat due to low discharge temperature 11 U9 UH Abnormality such as overvoltage or voltage shortage and abnor...

Page 15: ...ng phenomena takes place No signals from the remote controller are accepted OPE lamp is blinking The buzzer makes a short pipng sound Note Operation is not possible for about 30 seconds after cancella...

Page 16: ...ime displayed is the number of hours the filter has been used since the filter reset was performed 4 Press the FILTER button 5 The data is displayed in C Airflow temperature display example Flashing W...

Page 17: ...oducts Directive 2009 125 EC This product is designed and intended for use in the residential commercial and light industrial environment The product at hand is based on the following EU regulations R...

Reviews: