background image

4

3.  Installing the indoor unit

 PKA-RP·HAL

Fig. 3-6

B

A

C

E

D

3.2.3.  Installing the wall mounting fixture

 Since the indoor unit weighs near 13 kg, selection of the mounting 

location requires thorough consideration. If the wall does not seem to be 

strong enough, reinforce it with boards or beams before installation.

 The mounting fixture must be secured at both ends and at the centre, if 

possible. Never fix it at a single spot or in any nonsymetrical way.

  (If possible, secure the fixture at all the positions marked with a bold 

arrow.)

 Warning:

If possible, secure the fixture at all positions indicated with a bold arrow.

 Caution:

•  The unit body must be mounted horizontally.

•  Fasten at the holes marked with ▲ as shown by the arrows.

 PKA-RP·HAL (Fig. 3-4)

Min. 90 mm (617.6 mm or greater with optional drain pump installation)

Min. 200 mm

Min. 72 mm (142.5 mm or greater with left, rear left, or lower left piping, and optional drain 
pump installation)

Fixing screws (4 × 35) 

2

Level

Fasten a thread to the hole.

Place the level against the horizontal reference line of the mount board and mount so that it is 
level. Hang a weight from the thread and align with   EPK of the mount board to permit leveling.

Weight

Mount board 

1

3.3.  When embedding pipes into the wall (Fig. 3-5)

•  The pipes are on the bottom left.

•  When the cooling pipe, drain pipes internal/external connection lines etc are to 

be embedded into the wall in advance, the extruding pipes etc, may have to be 

bent and have their length modified to suit the unit.

•  Use marking on the mount board as a reference when adjusting the length of the 

embedded cooling pipe.

•  During construction, give the length of the extruding pipes etc some leeway.

Mount board 

1

Reference marking for flare connection

Through hole

On-site piping

3.4.  Preparing the indoor unit

*  Check beforehand because the preparatory work will differ depending on the 

exiting direction of the piping.

*  When bending the piping, bend gradually while maintaining the base of the 

piping exiting portion. (Abrupt bending will cause misshaping of the piping.)

Extraction and processing of the piping and wiring (Fig. 3-6)

1. Connection of indoor/outdoor wiring 

 See page. 8.

2. Wrap the felt tape 

3

 in the range of the refrigerant piping and drain hose which 

will be housed within the piping space of the indoor unit. 

•  Wrap the felt tape 

3

 securely from the base for each of the refrigerant piping 

and the drain hose. 

•  Overlap the felt tape 

3

 at one-half of the tape width. 

•  Fasten the end portion of the wrapping with vinyl tape.

Liquid pipe

Gas pipe

Indoor/outdoor connection cable

Drain hose

Felt tape 

3

3. Be careful that the drain hose is not raised, and that contact is not made with the 

indoor unit box body.  

Do not pull the drain hose forcefully because it might come out. 

Rear, right and lower piping (Fig. 3-7)

1) Be careful that the drain hose is not raised, and that contact is not made with 

the indoor unit box body.  

Arrange the drain hose at the underside of the piping and wrap it with felt 

tape 

3

2) Securely wrap the felt tape 

3

 starting from the base. (Overlap the felt tape at 

one-half of the tape width.) 

Cut off for right piping. 

Cut off for lower piping. 

Fig. 3-4

A

B

C

D

I

G

F

H

E

Fig. 3-5

B

A

C

D

Fig. 3-7

B

A

1)

2)

RG79D479H02_en.indd   4

2012/10/09 (火)   午前 11:37:51

Summary of Contents for Mr.Slim PKA-RP35HAL

Page 1: ...begint MANUALE DI INSTALLAZIONE Per un uso sicuro e corretto prima di installare il condizionatore d aria leggere attentamente il presente manuale ed il manuale d installazione dell unit esterna MANU...

Page 2: ...changes or dripping water When the room humidity exceeds 80 or when the drainpipe is clogged water may drip from the indoor unit Do not install the indoor unit where such dripping can cause damage Whe...

Page 3: ...am to the left The hole should incline so that the outside opening is lower than the inside opening Insert a sleeve with a 75 mm diameter and purchased locally through the hole A Sleeve B Hole C Indoo...

Page 4: ...rking on the mount board as a reference when adjusting the length of the embedded cooling pipe During construction give the length of the extruding pipes etc some leeway A Mount board 1 B Reference ma...

Page 5: ...ve the indoor unit to the left and right and verify that the indoor unit is hung securely 5 Fasten by pushing the bottom part of the indoor unit onto the mount board 1 Fig 3 10 Check that the knobs on...

Page 6: ...6 35 17 14 18 12 7 28 49 61 PKA RP HAL Fig 4 3 B A 4 2 Indoor unit Refrigerant and Drainage Piping Sizes Item Model PKA RP35 RP50HAL Refrigerant piping Liquid OD 6 35 1 4 Gas OD 12 7 1 2 Drainage pip...

Page 7: ...r H Drainage ditch I 5 cm or less between the end of drain pipe and the ground J Drain hose K Soft PVC hose Inside diameter 15 mm or Hard PVC pipe VP 16 Bond with PVC type adhesive Preparing left and...

Page 8: ...te control cord J Indoor outdoor connection cord K Hook L Ground wire connection portion Warning Never splice the power cable or the indoor outdoor connection cable otherwise it may result in a smoke...

Page 9: ...ize must comply with the applicable local and national code 2 Power supply cords and Indoor unit Outdoor unit connecting cords shall not be lighter than polychloroprene sheathed flexible cord Design 2...

Page 10: ...door unit DIP switch settings when using separate indoor unit outdoor unit power supplies only ON OFF 1 2 SW8 3 There are three types of labels labels A B and C Affix the appropriate labels to the uni...

Page 11: ...he min button twice continuously Pair No 0 blinks 3 Press the temp button to set the pair number you want to set 4 Press the SET button with something sharp at the end Set pair number is lighted for t...

Page 12: ...ly 6 Complete function selection Direct the wireless remote controller toward the sensor of the indoor unit and press the button E Note Whenever changes are made to the function settings after install...

Page 13: ...mode then check whether warm air is blown out from the unit 5 Press the FAN button and check whether fan speed changes 6 Press the VANE button and check whether the auto vane operates properly 7 Press...

Page 14: ...U6 Compressor overcurrent interruption Abnormal of power module 10 U7 Abnormality of super heat due to low discharge temperature 11 U9 UH Abnormality such as overvoltage or voltage shortage and abnor...

Page 15: ...ng phenomena takes place No signals from the remote controller are accepted OPE lamp is blinking The buzzer makes a short pipng sound Note Operation is not possible for about 30 seconds after cancella...

Page 16: ...ime displayed is the number of hours the filter has been used since the filter reset was performed 4 Press the FILTER button 5 The data is displayed in C Airflow temperature display example Flashing W...

Page 17: ...oducts Directive 2009 125 EC This product is designed and intended for use in the residential commercial and light industrial environment The product at hand is based on the following EU regulations R...

Reviews: