
28
29
10-1-2. How to set rotation function (Back-up function, 2nd stage cut-in function)
You can set these functions by wired remote controller. (Maintenance monitor)
Both main and sub unit should be set in same setting.
Every time replacing indoor controller board for servicing, the function should be set again.
NOTICE
Setting No.
(Request code)
Setting contents
Initial
setting
No.1
(310)
Monitoring the request code of current setting
No.2
(311)
Rotation and Back-up OFF (Normal group control operation)
No.3
(312)
Back-up function only
No.4
(313)
Rotation ON (Alternating interval = 1day) and back up function
No.5
(314)
Rotation ON (Alternating interval = 3day) and back up function
No.6
(315)
Rotation ON (Alternating interval = 5day) and back up function
No.7
(316)
Rotation ON (Alternating interval = 7day) and back up function
No.8
(317)
Rotation ON (Alternating interval = 14day) and back up function
No.9
(318)
Rotation ON (Alternating interval = 28day) and back up function
Setting No.
(Request code)
Setting contents
Initial
setting
No.1
(320)
Monitoring the request code of current setting
No.2
(321)
Cut-in function OFF
No.3
(322)
Cut-in Function ON(Set point = Set temp.+ 4°C(7.2°F))
No.4
(323)
Cut-in Function ON(Set point = Set temp.+ 6°C(10.8°F))
No.5
(324)
Cut-in Function ON(Set point = Set temp.+ 8°C(14.4°F))
(1) Request Code List
Rotation setting
2nd stage cut-in setting
OCH492A