Mitsubishi Mr.Slim PCA-RP125HAQ Service Manual Download Page 21

21

   (For the separate indoor/outdoor unit power sup-

ply system)

1

 Power supply of 220–240 V AC is not supplied to 

indoor unit.

2

 The connectors of the optional replacement kit are 

not used.

3

 Defective indoor controller board

4

 Defective indoor power board

9-3. TROUBLESHOOTING BY INFERIOR PHENOMENA 

Note: Refer to the manual of outdoor unit for the detail of remote 

         controller.

Phenomena

Cause

Countermeasure

(1)LED2 on indoor controller board 

    is off.

 • When LED1 on indoor controller board is also off.

1

 Power supply of rated voltage is not supplied to out-

door unit.

2

 Defective outdoor controller circuit board

3

 Power supply of 220–240 V is not supplied to indoor 

unit

4

 Defective indoor power board

5

 Defective indoor controller board

1

 Check the voltage of outdoor power 

  supply terminal block (L, N) or (L3, N).

• When 220–240 V AC is not detected.

      Check the power wiring to outdoor unit  

      and the breaker.

• When 220–240 V AC is detected. 

  —Check 

2

 (below).

2

 Check the voltage between outdoor 

  terminal block S1 and S2.

• When 220–240 V AC is not detected.

  Check the fuse on outdoor controller cir-

cuit board.

      Check the wiring connection.

• When 220–240 V AC is detected. 

  —Check 

3

 (below).

3

 Check the voltage between indoor terminal 

block S1 and S2.

• When 220–240 V AC is not detected.

      Check indoor/outdoor unit connecting  

      wire for mis-wiring.

• When 220–240 V AC is detected. 

  —Check 

4

 (below).

4

 Check voltage output from CN2S on indoor 

power board (13.1 V DC).  Refer to "9-6-1. 

Power board".

• When no voltage is output.

      Check the wiring connection.

• When output voltage is between 12.5 V DC 

and 13.7 V DC. 

  —Check 

5

 (below).

5

 Check the wiring connection between indoor 

controller board and indoor power board. 

Check the fuse on indoor controller board. 

If no problems are found, indoor controller 

board is defective.

 • When LED1 on indoor controller board is lit.

1

 Mis-setting of refrigerant address for outdoor unit

(There is no unit corresponding to refrigerant 

address “0”.)

1

 Reconfirm the setting of refrigerant address 

for outdoor unit

Set the refrigerant address to “0”.

(For grouping control system under which 

2 or more outdoor units are connected, set 

one of the units to “0”.)

Set refrigerant address using SW1 (3-6) on 

outdoor controller circuit board.

1

 Check the voltage of indoor power supply 

terminal block (L,N).

• When 220–240 V AC is not detected.

  Check the power supply wiring.

• When 220–240 V AC is detected.

  -Check 

2

 (below).

2

 Check that there is no problem in the meth-

od of connecting the connectors.

• When there are problems in the method of 

connecting the connectors.

  Connect the connector correctly referring 

to installation manual of an optional kit.

• When there is no problem in the method 

of connecting the connectors.

  -Check 

3

 (below).

3

 Check voltage output from CNDK on indoor 

controller board.

• When 220–240 V AC is not detected.

  Check the fuse on indoor controller board.

  Check the wiring connection between 

indoor power supply terminal block and 

CND on indoor controller board.

• When 220–240 V AC is detected.

  -Check 

4

 (below).

4

 Check voltage output from CN2S on indoor 

power board.

• When no voltage output.

  Check the wiring connection between

  CNDK on indoor controller board and

  CNSK on indoor power board.

  If no problem are found, indoor power 

board is defective.

• When 12.5–13.7 V DC is detected.

  Check the wiring connection between 

CN2S on indoor power board and

  CN2D on indoor power board.

  If no problem is found, indoor controller 

board is defective.

OCH492A

Summary of Contents for Mr.Slim PCA-RP125HAQ

Page 1: ...REFRIGERANT SYSTEM DIAGRAM 15 9 TROUBLESHOOTING 16 10 SPECIAL FUNCTION 27 11 DISASSEMBLY PROCEDURE 32 ON OFF TEMP July 2014 Model name indication Indoor unit Model Name PCA RP71HAQ PCA RP125HAQ PARTS...

Page 2: ...140 250YKA OCH451 OCB451 PU H P71VHAR3 PU H P71 125 140YHAR3 PU H P71VHAR3 UK PU H P71 125 140YHAR3 UK OC379 PUHZ P125 140VHA3R2 PUHZ P125 140YHAR1 PUHZ P125 140VHA3R2 UK PUHZ P125 140YHAR1 UK OCH415...

Page 3: ...se a refrigerant other than R407C If another refrigerant R22 etc is used the chlorine in the refrigerant may cause the lubricant deterioration Use a vacuum pump with a reverse flow check valve The vac...

Page 4: ...erant Gravimeter Unit 1 Cautions for service After recovering the all refrigerant in the unit proceed to working Do not release refrigerant in the air After completing the repair service recharge the...

Page 5: ...ntamination inside refrigerant piping can cause deterio ration of refrigerant oil etc If dirt dust or moisture enter into refrigerant cycle that can cause deterioration of refrigerant oil or malfuncti...

Page 6: ...ls for R410A refrigerant Gravimeter Unit No Tool name Specifications 1 Gauge manifold Only for R410A Use the existing fitting specifications UNF1 2 Use high tension side pressure of 5 3MPa G or over 2...

Page 7: ...he Installation Manual All icons are displayed for explanation 5 6 1 2 3 4 Press to turn ON OFF the indoor unit 1 ON OFF button This lamp lights up in green while the unit is in operation It blinks wh...

Page 8: ...gistered in advance to be displayed Maintenance Auto descending panel Auto descending panel Optional parts Up Down you can do Manual vane angle Use to set the vane angle for each vane to a fixed posit...

Page 9: ...et If the simple or Auto Off timer is set the time to be switched off is shown Sensor indication Displays when the remote controller sensor is used Locked indicator Indicates that remote controller bu...

Page 10: ...8 1 060 1 350 0 direct blow Remote controller built in 44 50 26 1 1 520 59 7 8 650 25 5 8 280 11 56 124 Cooling 0 09 0 43 0 86 Heating 0 09 0 43 0 86 Single phase 50Hz 230V Stainless steel Plate fin c...

Page 11: ...QUENCIES Hz PCA RP71HAQ PCA RP71HAQ ER NOTCH High Low SPL dB 38 34 LINE 90 80 70 60 50 40 30 20 10 63 125 250 500 1000 2000 4000 8000 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE NC 60 NC 50...

Page 12: ...owing clearances gas liquid Suspension bolt 130 210 45 165 120 1224 1180 75 1136 986 1098 70 243 254 175 197 110 21 130 15 258 110 102 320 80 90 140 18 75 70 90 650 13 289 75 280 495 43 295 2 2 2 2 0...

Page 13: ...90 650 300 100 1520 100 Electrical box 500 250 2 3 gas liquid Suspension bolt 70 243 254 175 197 110 21 130 15 258 1482 110 102 1370 75 1608 320 80 1564 1520 90 120 140 18 75 70 90 650 13 289 75 280 4...

Page 14: ...For power supply system of this unit refer to the caution label located near this diagram 7 1 3 5 LED3 LED2 LED1 t t t The black square indicates a switch position S1 S2 S3 S1 S2 S3 S1 S2 S3 S1 S2 1 2...

Page 15: ...rainer 50 Condenser evaporator temperature thermistor TH5 Room temperature thermistor TH1 Refrigerant flow in cooling Refrigerant flow in heating Strainer 50 Strainer 50 Heat exchanger Refrigerant GAS...

Page 16: ...t troubleshooting and ascertain the cause of the trouble according to 9 3 TROUBLESHOOTING BY INFERIOR PHENOMENA The trouble is not reoccurring Logged Not logged 1Consider the temporary defects such as...

Page 17: ...rmal if the unit does not reset normally after 3 min utes The unit returns to normal opera tion if it has been reset normally 2 Constantly detected during cooling drying and heating operation Short 90...

Page 18: ...otor is defective Indoor controller board is defec tive 5 Defective outdoor fan control 6 Overcharge of refrigerant 7 Defective refrigerant circuit clogs 8 Bypass circuit of outdoor unit is defective...

Page 19: ...g remote control ler max 2 units When it is not the above mentioned problem of 1 3 4 Diagnose remote controllers a When RC OK is displayed Remote controllers have no problem Turn the power off and on...

Page 20: ...short circuit or miswiring converse wiring of indoor outdoor unit connecting wire 2 Defective transmitting receiving circuit of indoor controller board 3 Defective transmitting receiving circuit of i...

Page 21: ...tion between indoor controller board and indoor power board Check the fuse on indoor controller board If no problems are found indoor controller board is defective When LED1 on indoor controller board...

Page 22: ...izontal regardless of remote control 2 Check 2 left Check the vane motor Refer to How to check the parts Check for breaking of wire or connec tion failure of connector Check Up down vane setting Unit...

Page 23: ...with a tester At the ambient temperature 10 to 30 Refer to the Thermistor Characteristic Graph below Room temperature thermistor TH1 Pipe temperature thermistor liquid TH2 Condenser evaporator temper...

Page 24: ...9 6 1 Power board PCA RP71HAQ PCA RP125HAQ PCA RP71HAQ ER CNSK Connect to the indoor controller board CNDK Between 1 to 3 220 240 V AC CN2S Connect to the indoor controller board CN2D Between 1 to 3 1...

Page 25: ...al 13 V pulse input 1 3 4 Operation indicator 13 V DC 3 3 5 Malfunction indicator 13 V DC 3 CN6V Vane motor output MV CN105 CN90 Connect to the wire less remote controller board CNB CN31 Drain sensor...

Page 26: ...ft in the table indicates the jumper line is disco nnected There is no jumper JP1 because these models have the cond eva temperature thermistor TH5 Marks in the table below Jumper wire Short Open With...

Page 27: ...ding to the interval of rotation setting Main and sub unit should be set by refrigerant address Outdoor DIP switch setting Refrigerant address 00 Main unit Refrigerant address 01 Sub unit When an erro...

Page 28: ...val 1day and back up function No 5 314 Rotation ON Alternating interval 3day and back up function No 6 315 Rotation ON Alternating interval 5day and back up function No 7 316 Rotation ON Alternating i...

Page 29: ...en D when Maintenance monitor is activated The display D now allows you to set a request code No 4 Press the TEMP and buttons 4 to select the desired refrigerant address 5 Press the CLOCK and buttons...

Page 30: ...button and press the button Set the Refrigerant address and Request code Select the item to be changed with the F1 or F2 button Select the required setting with the F3 or F4 button Select the required...

Page 31: ...tton Select the required setting with the F3 or F4 button Press the F3 or F4 button to set the Refrigerant address 0 Press the F3 or F4 button to set the desired request code No Rotation Back up opera...

Page 32: ...sen the screw for control box cover to remove the control box cover See Photo 2 3 Remove the lead wire from the 2 clips 4 Remove the 2 white cord heater relay connectors 1P o 2 and 2 fan motor relay c...

Page 33: ...connectors 6P in the control box See Photo 3 4 Remove the 3 filter rails See Photo 1 4 5 Remove the fan guard See Photo 5 6 Remove the lower casing See Photo 6 7 Remove the green earth wire from the...

Page 34: ...n and remove the drain pan Note Remove the drain pan carefully since the drain could remain in it 7 Removing the under panel 1 Remove the oil filter See Figure 1 2 Remove the 3 filter rails See Photo...

Page 35: ...der panel See Photo 11 4 Remove the drain pan See Photo 12 5 Remove the 2 screws 4 10 for pipe cover and remove the pipe cover See Photo 15 6 Remove the 3 screws 4 10 left 2 right 1 for heat exchanger...

Page 36: ...KYO 100 8310 JAPAN CCopyright 2010 MITSUBISHI ELECTRIC CORPORATION Distributed in Jul 2014 No OCH492 REVISED EDITION A Distributed in Dec 2010 No OCH492 Made in Japan New publication effective Jul 201...

Reviews: