11.3 Battery Life and Replacement Procedure
The battery installed in the CPU module is used for data retention during the power failure
of the program memory and error/operation history. Special relays SM51 and SM52 turn
on due to the decrease of battery voltage. Even if the special relays turn on, the program
and error/operation history data are not erased immediately.
After relay SM51 turns on, replace the battery quickly within the data retention time for
power failure (3 minutes).
POINT
SM51 turns on when the battery voltage falls below the specified value, and
remains ON even after the voltage is recovered to the normal value.
SM52 turns on when the battery voltage falls below the specified value, and turns
OFF when the voltage is recovered to the normal value.
After SM51 and/or SM52 turns on, replace the battery quickly.
SM51 and SM52 turn on when the battery voltage of the CPU module is lowered.
The battery voltage drop can be checked with the contents of the special registers SD51
and SD52.
For details of SD51 and SD52, refer to Section 12.7.
Figure 11.1 Bit pattern
When the battery
voltage is low, the
value is "1."
SD51, SD52
b15
b1 b0
to
Fixed at 0
Error of a CPU
module battery