Error
Code
(SD0)
Error Contents and Cause
Corrective Action
Corresponding
CPU
5001
The program scan time exceeded the
WDT value specified in the PLC RAS
setting of the PLC parameter dialog
box.
Read the individual information of the
error with the GX Developer, check its
value (time), and shorten the scan time.
QS
5010
The program scan time exceeded the
constant scan time specified in the PLC
RAS setting of the PLC parameter
dialog box.
Review the constant scan time in the
PLC parameter so that the margin time
of constant scan may be fully reserved.
QS