9
EMC AND LOW VOLTAGE DIRECTIVES
9.2 Requirement to Conform to the Low Voltage Directive
9.2.1 Standard applied for MELSEC-QS series PLC
9
- 9
9
EM
C AN
D
LO
W
VOL
TA
G
E
DI
RE
C
T
IVES
10
LO
ADING A
N
D
INST
AL
LA
TION
11
M
A
INTE
NA
NCE
AND
IN
SPE
CTI
O
N
12
TR
OU
BL
ESH
OO
TIN
G
A
P
P
E
NDICE
S
INDE
X
9.2 Requirement to Conform to the Low Voltage Directive
The Low Voltage Directive requires each device that operates with the power supply
ranging from 50 to 1000VAC and 75 to 1500VDC to satisfy the safety requirements.
In Section 9.2.1 to Section 9.2.6, cautions on installation and wiring of the MELSEC-QS
series PLC to conform to the Low Voltage Directive are described.
These descriptions are based on the requirements and standards of the regulation,
however, it does not guarantee that the entire machinery manufactured based on the
descriptions conforms to the above-mentioned directive. The method and judgment for the
conformity to the low voltage directive must be left to the manufacturer's own discretion.
9.2.1 Standard applied for MELSEC-QS series PLC
The standard applied for MELSEC-QS series PLC is EN61131-2 safety of devices used in
measurement rooms, control rooms, or laboratories.
The MELSEC-QS series PLC modules which operate at the rated voltage of 50VAC/
75VDC or above are also developed to conform to the above standard.
The modules which operate at the rated voltage of less than 50VAC/75VDC are out of the
Low Voltage Directive application range.
For products with the CE mark, refer to the "Standard Compliance" menu of the
MELFANSweb homepage.
9.2.2 MELSEC-QS series PLC selection
(1) Power supply module
There are dangerous voltages (voltages higher than 42.4V peak) inside the power
supply modules of the 100/200VAC rated input voltages. Therefore, the CE marked
models are enhanced in insulation internally between the primary and secondary.
(2) CPU module, base unit
Using 5VDC circuits inside, the above modules are out of the Low Voltage Directive
application range.
(3) CC-Link Safety master module, CC-Link IE controller network module,
MELSECNET/H module, Ethernet module
These modules are out of the scope of the Low Voltage Directive because the rated
voltage is 24VDC or less.