4. Using Test Mode
4.5 Test Menu 5:
Pulse Output Operation Test
The following operations are available in the test mode.
・
When the ME-4210-SS96 optional plug-in module is not installed, this test menu will be skipped.
・
When
⑨
Pulse/Alarm output 1(Setting Menu 5) and
⑫
Pulse/Alarm output 2(Setting Menu 5) is not set to "PULSE",
this test menu will be skipped.(ME-4210-SS96)
Set the test menu number to "5".
Test menu
SET
DISPLAY
Execute the operation test for pulse output CH1.
(Input is not necessary.)
When
is pressed, 1 pulse is output.
- 46 -
<To continue other test mode>
⇒
Select other test menu number and then press
.
<To close test mode>
⇒
Select "End" as the test menu number and then press .
You will return to the operation mode.
Test menu
SET
SET
SET
SET
DISPLAY
①
Pulse output CH1
operation test
0
1
2
・・・
49
50
[
pulse
]
RESET
RESET
Note1: When Pulse/Alarm output 1(Setting Menu 5) is not set to "PULSE",
Upper :Pulse output 1
Middle :Pulse Unit set up with setting menu 5.9.2.
Lower
Left :The number of output pulses
Right :(Pulse Unit)×(The number of output pulses)
this display will be skipped.(ME-4210-SS96)
Note2: Output is executed according to the set pulse width.
Note3:
After reaching 50,
the number of output pulses
returns t o 1.
Execute the operation test for pulse output CH2.
The test method is the same as
①
Pulse Output CH1 Operation Test .
②
Pulse output CH2
operation test
Note: When Pulse/Alarm output 2(Setting Menu 5) is not set to "PULSE",
this display will be skipped.(ME-4210-SS96)