The following shows a simple setting example.
■
Setting Example
Model:
ME96SSR-MB
(
Not option unit
)
Phase wire system : 3-phase 4-wire
Measuring element :
A, V, W, PF
Input
Voltage
:220/380V
CT primary current : 200A
CT Secondary current:5A
frequency
:50Hz
MODBUS
®
RTU
:
address
1,
baud rates
19.2kbps,
parity
even,
stop bit
1
■
Setting Procedure
Items of which setting value need to be changed are indicated by .
Operation Mode
Note: For more details about setting contents, refer to pages 15 to 20.
- 39 -
Set the setting menu number to "1" and then press S E T .
Setting menu
Press
+
simultaneously for 2seconds
RESET
SET
The factory default setting is "3-phase 4-wire," so just press SET.
Phase wire system
SET
Setting is "P01," so just press SET.
Display pattern
SET
The factory default setting is "No VT," so just press SET.
VT/direct voltage
selection
SET
The factory default setting is "220/380V," so just press .
Direct voltage
SET
The factory default setting is "5A," so just press SET.
CT secondary
current
SET
Set to "200A" and then press SET.
CT primary
current
SET
The factory default setting is "50Hz," so just press SET.
frequency
SET
The factory default setting is "0 second," so just press SET
.
Time constant for
current demand
SET
Set the setting menu number to "2" and then press SET .
Setting menu
SET
SET