10 - 4
10.1 GOT Restoration Sheet
(2) Status of the GOT when it freezes (screen operation stopped)
(3) Status of the PLC CPU
Phenomenon
Cause/status
Action
(a) Switching to the utility
Enabled
Error code (system alarm):
( )
Example: 460 Communication unit error
When the system alarm display function
can be used, take the action for the error
code (system alarm) displayed.
If the action cannot be taken, proceed to
(2)-(b).
Disabled
The system alarm display function cannot be
used.
Proceed to (2)-(c).
(b) Executing of I/O check from the GOT utility
Communication error
Display details:
( )
Example: A message indicating the cause may be
a connection error was displayed.
Proceed to (2)-(c).
No error
The hardware such as a communication interface
has no error.
Proceed to (3) Status of the PLC CPU.
(c) Objects not displayed on the monitor screen
Found
Details:
( )
Example: The numerical display object is not
displayed.
Proceed to (3) Status of the PLC CPU.
Not found
Phenomenon
Cause/status
Action
(a) PLC failure
Occurs always.
An error such as CONTROL-BUS. ERROR or SP.
UNIT LAY. ERROR may have occurred.
Error code (system alarm):
( )
Example: 1204 CPU H/W fault
Proceed to the following.
Occurs sometimes.
The PLC CPU may be influenced by noise or the
hardware may be faulty.
Occurrence frequency:
( )
Example: Once a month
Error code (system alarm):
( )
Example: 1204 CPU H/W fault
Proceed to (4) GOT restoration
procedure.
Operates normally.
Summary of Contents for GOT 1000 GT16
Page 1: ...GT16 User s Manual Hardware ...
Page 2: ......
Page 14: ...A 12 INDEX REVISIONS WARRANTY ...
Page 210: ...App 17 ...
Page 212: ...Index 2 Transportation Precautions App 15 U USB environmental protection cover 2 17 8 19 ...
Page 217: ......