FX
2N
-32CCL CC-Link Interface Block
Connection and Wiring 3
3-4
Wiring of twisted pair cable
Wire the FX
2N
-32CCL and the CC-Link using shielded twisted pair cables as shown in the figure below.
•
Connect the terminals DA and DA, DB and DB as well as DG and DG of each station with shielded
twisted pair cables. Because two DA terminals and two DB terminals are provided in the FX
2N
-32CCL,
a next station can be easily connected.
•
Connect the SLD terminal of each station to a shield of a shielded twisted pair cable.
•
Perform Class 3 grounding to the FG terminal of each station.
•
Wiring of each station can be performed from any point without regard to the station No.
•
When the FX
2N
-32CCL is used as the terminal station, connect a terminal resistor between the terminals
DA and DB of the FX
2N
-32CCL. The terminal resistor is packed together with the Master unit.
•
The maximum transmission distance and the distance between stations in the CC-Link system vary
depending on the selected transmission speed. For the details, refer to the maximum transmission dis-
tance described in "2.2 General specifications and performance specifications" or the specifications
described in the manual of the CC-Link master unit.
D A
D B
D G
S L D
F G
D A
D A
D B
D B
D G
S L D
F G
D A
D B
D G
S L D
F G
C la ss 3
g ro u n ding
C la ss 3
g ro u n ding
T erm in a l
res isto r
T erm in a l
res isto r
M as ter
u n it
F X
2 N
-32 C C L
R em o te I/O
u n it
S hie lde d tw isted
p air c ab le
C la ss 3
g ro u n ding
Summary of Contents for FX2N-32CCL
Page 1: ...USER S MANUAL CC Link INTERFACE BLOCK FX2N 32CCL ...
Page 18: ...FX2N 32CCL CC Link Interface Block Specifications 2 2 6 Memo ...
Page 26: ...FX2N 32CCL CC Link Interface Block Setting of Remote Device Stations 4 4 4 Memo ...
Page 39: ...FX2N 32CCL CC Link Interface Block Assignment of Buffer Memory BFM 5 5 13 ...
Page 54: ...FX2N 32CCL CC Link Interface Block Programming Examples 6 6 14 Memo ...