5. Wiring

Cautions on wiring

Make sure to shut down the power supplies of all phases on the outside before starting installation 
or wiring.
If the power supplies are not shut down, you may receive an electrical shock or the unit may be 
damaged.

As to loads, such as a connector for normal rotation and a connector for reverse rotation, 
which are dangerous when turning on at the same time, make sure to interlock them outside 
the PLC in addition to interlocking of them in a program in the PLC.

Correctly connect the power cable of the FX

2N

-2LC and the PLC as described in this manual.

If the AC power supply is connected to a DC I/O terminal or DC power terminal, the PLC may 
be damaged.

Perform Class D grounding with an electric wire of 2 mm

2

 or more to the grounding terminal in the 

FX

2N

-2LC and the PLC. However, never perform common grounding with a strong power system.

6. Specifications

6.1 General specifications

Other General specifications are equivalent to those for the PLC main unit. Refer to the manual of the PLC
main unit.

6.2 Power supply specifications

Item

Specifications

Withstand voltage

500V AC for 1 minute 
(between analog input terminal and grounding terminal)

Item

Specifications

Driving power supply

24V DC (-15% to +10% maximum), input from driving power 
supply terminal

Power supply for 
communication

5V DC (supplied from inside of PLC main unit)

Current consumption

24V DC, 55 mA and 5V DC, 70 mA

Insulation method

Analog input area and PLC are insulated by photocoupler.
Power supply and analog input are insulated by DC/DC converter.
(Channels are insulated from each other.)

Number of occupied 
I/O points

8 points in total (including input points and output points)

    PTA/

FG

PTB/TC+

PTB/TC-

FX

2N

-2LC

Resistance
thermometer bulb

Shielded cable

24+

24-

OUT1

COM

OUT2

CT

CT

    PTA/

FG

PTB/TC+

PTB/TC-

CT

CT

    PTA/

FG

PTB/TC+

PTB/TC-

SSR

SSR

FX

2N

-2LC

DC24V

+

-

CT

CT

Heater

Heater

Shielded cable

Thermocouple

AC power
supply

Shielded cable

Thermocouple

*1

When a temperature sensor is a thermocouple

When a temperature sensor is a resistance thermometer bulb

*1 Connect the ground terminals of

the FX

2N

-2LC unit and the main

unit. Use class D grounding on
the main unit.

Use the compensating cable 
when you use the thermo couple.

The temperature sensor must use 
three line type.
The resistance of the lead wire is a 
little, and use the wire rod without 
the resistance difference between 
three lines.

Secure the termination using a 
tightening torque of 0.5 to 0.8N

x

m

6.3 Performance specifications

6.4 Input specifications

6.5 Input range

Item

Description

Control method

Two-position control, PID control (with auto tuning function), PI control

Control operation 
period

500ms

Set temperature 
range

Equivalent to input range

Heater disconnection 
detection

Alarm is detected by buffer memory 
(Variable within range from 0.0 to 100.0 A.).

Operation mode 

0: Measured value monitor
1: Measured value m Temperature alarm 
2: Measured value m Temperature alarm + Control 
    (selected by buffer memory)

Self-diagnosis 
function

Adjustment data check, input value check, watch dog timer check.

Memory

Built-in EEPROM (Number of times of overwrite: 100,000 times)

Indication

POWER

Lit (green): While 5V power is supplied

Extinguished: While 5V power is not supplied

24V

Lit (red): While 24V power is supplied

Extinguished: While 24V power is not supplied 

OUT1

Lit (

red

): While control output 1 is ON

Extinguished: While control output 1 is OFF

OUT2

Lit (red): While control output 2 is ON

Extinguished: While control output 2 is OFF

Item

Description

Tempera-
ture input

Number of input points

2 points

Input 
type

Thermocouple 

K, J, R, S, E, T, B, N, PLII, WRe5-26, U, L, JIS C 1602-1995

Resistance ther-
mometer bulb

3-wire Pt100 JIS C 1604-1997, JPt100 JIS C 1604-1981

Measurement precision

Ambient temperature 23 

°

C ± 5 

°

C : ± 0.3% of range span ± 1 digit.

Ambient temperature 0 

°

C to 55 

°

C : ± 0.7% of range span ± 1 digit.

However, 0 to 399 

°

C (0 to 799 

°

F) in B inputs as well as 0 to 32 

°

F in 

PLII and WRe5-26 inputs are outside precision guarantee range.

Cold contact tempera-
ture compensation error

Within ±1.0 

°

However, within ± 2.0 

°

C while input value is -150 to -100 

°

C

within ± 3.0 

°

C while input value is -200 to -150 

°

C

Resolution

0.1 

°

C (0.1

°

F) or 1 

°

C(1

°

F)  (Varies depending on input range of used 

sensors.) 

Sampling period

500ms

Effect of external resis-
tance

Approx. 0.35 

µ

V/

Input impedance

1 M

 or more

Sensor current

Approx. 0.3 mA

Allowable input lead wire 
resistance

10 

 or less

Operation when input is 
disconnected

Upscale

Operation when input is 
short-circuited

Downscale

CT input

Number of inputs

2 points

Current detector

CTL-12-S36-8 or CTL-6-P-H (manufactured by U.R.D. Co., Ltd.)

Heater current 
measurement value

When CTL-12 is used: 0 to 100A       When CTL-6 is used: 0 to 30A

Measurement precision

Larger one between ± 5% of input value and 2 A 
(excluding precision of current detector)

Sampling period

1 second

Sensor type

K

J

R

S

Input range

-200.0 to 200.0 

°

C

-100.0 to 400.0 

°

C

-100 to 1300 

°

C

-100 to 800 

°

F

-100 to 2400 

°

F

-200.0 to 200.0 

°

C

-100.0 to 400.0 

°

C

-100.0 to 800.0 

°

C

-100 to 1200 

°

C

-100 to 1600 

°

F

-100 to 2100 

°

F

0 to 1700 

°

C

0 to 3200 

°

F

0 to 1700 

°

C

0 to 3200 

°

F

Sensor type

E

T

B

N

Input range

-200.0 to 200.0 

°

C

 0 to 1000 

°

C

0 to 1800 

°

F

-200.0 to 200.0 

°

C

-200.0 to 400.0 

°

C

   0.0 to 400.0 

°

C

-300.0 to 400.0 

°

F

-300.0 to 700.0 

°

F

   0.0 to 700.0 

°

F

0 to 1800 

°

C

0 to 3000 

°

F

0 to 1300 

°

C

0 to 2300 

°

F

When B is used, 0 to 399

 

°

C

 (0 to 799 

°

F) is outside the precision guarantee range.

When PLII is used, 0 to 32

 

°

F is outside the precision guarantee range.

When WRe5-26 is used, 0 to 32

 

°

F is outside the precision guarantee range.

6.6 Output specifications

Sensor type

PLII

WRe5-26

U

L

Input range

0 to 1200 

°

C

0 to 2300 

°

F

0 to 2300 

°

C

0 to 3000 

°

F

-200.0 to 600.0 

°

C

-300.0 to 700.0 

°

F

0.0 to 900.0 

°

C

0 to 1600 

°

F

Sensor type

JPt100

Pt100

Input range

 -50.0 to 150.0 

°

C

-200.0 to 500.0 

°

C

-300.0 to 300.0 

°

F

-300 to 900 

°

F

 -50.0 to 150.0 

°

C

-200.0 to 600.0 

°

C

-300.0 to 300.0 

°

F

-300 to 1100 

°

F

Item

Description

Number of output points

2 points

Output method

Open collector transistor output

Rated load voltage

5 to 24V DC

Maximum load voltage

30V DC or less

Maximum load current 

100mA

Leak current in OFF status

0.1 mA or less 

Maximum voltage drop in ON status

2.5V (maximum) or 1.0V (typical) at 100 mA

Control output cycle

30 seconds (Variable within range from 1 to 100 seconds)

Guidelines for the safety of the user and protection of the FX

2N

-2LC 

This manual has been written to be used by trained and competent personnel. This is defined
by the European directives for machinery, low voltage and EMC.

If in doubt at any stage during the installation of the FX

2N

-2LC always consult a professional

electrical engineer who is qualified and trained to the local and national standards. If in doubt
about the operation or use of the FX

2N

-2LC please consult the nearest Mitsubishi Electric

distributor. 

Under no circumstances will Mitsubishi Electric be liable or responsible for any consequential
damage that may arise as a result of the installation or use of this equipment. 

All examples and diagrams shown in this manual are intended only as an aid to understanding
the text, not to guarantee operation. Mitsubishi Electric will accept no responsibility for actual
use of the product based on these illustrative examples. 

Owing to the very great variety in possible application of this equipment, you must satisfy
yourself as to its suitability for your specific application. 

Manual number : JY992D85601

Manual revision : C

Date

: March 2007

JY992D85601C

Effective March 2007

Specifications are subject to 
change without notice

Summary of Contents for FX2N-2LC

Page 1: ...separately supplied Description FX2N 2LC USER S MANUAL JY992D85601 Additional Manual Describes the specification wiring installation of FX2N 2LC FX2N HARDWARE MANUAL JY992D66301 Supplied with product Describes the specification wiring and installation of FX2N series PLC FX2NC HARDWARE MANUAL JY992D76401 Supplied with product Describes the specification wiring and installation of FX2NC series PLC F...

Page 2: ... block to control outputs of temperature inputs from thermocouples and platinum resistance thermometer bulbs by PID control Connect the FX2N 2LC to the FX1N FX2N FX2NC FX3U Series PLC 1 As input sensors two thermocouples two platinum resistance thermometer bulbs or one thermocouple and one platinum resistance thermometer bulb are available 2 Data can be read and written using FROM TO instructions ...

Page 3: ... rail Align the upper side of the DIN rail mounting groove of the FX2N 2LC with a DIN rail DIN46277 width 35 mm and push it on the DIN rail When removing the FX2N 2LC pull out downward the DIN rail mounting hook and remove from DIN rail 3 2 Direct installation on panel surface Screw tighten the FX2N 2LC with M4 screws to a panel surface using two upper and lower mounting holes provided on the left...

Page 4: ...ints in total including input points and output points PTA FG PTB TC PTB TC FX2N 2LC Resistance thermometer bulb Shielded cable 24 24 OUT1 COM OUT2 CT CT PTA FG PTB TC PTB TC CT CT PTA FG PTB TC PTB TC SSR SSR FX2N 2LC DC24V CT CT Heater Heater Shielded cable Thermocouple AC power supply Shielded cable Thermocouple 1 When a temperature sensor is a thermocouple When a temperature sensor is a resist...

Page 5: ...3 C 5 C 0 3 of range span 1 digit Ambient temperature 0 C to 55 C 0 7 of range span 1 digit However 0 to 399 C 0 to 799 F in B inputs as well as 0 to 32 F in PLII and WRe5 26 inputs are outside precision guarantee range Cold contact tempera ture compensation error Within 1 0 C However within 2 0 C while input value is 150 to 100 C within 3 0 C while input value is 200 to 150 C Resolution 0 1 C 0 1...

Page 6: ... transistor output Rated load voltage 5 to 24V DC Maximum load voltage 30V DC or less Maximum load current 100mA Leak current in OFF status 0 1 mA or less Maximum voltage drop in ON status 2 5V maximum or 1 0V typical at 100 mA Control output cycle 30 seconds Variable within range from 1 to 100 seconds Guidelines for the safety of the user and protection of the FX2N 2LC This manual has been writte...

Page 7: ...nput points and two transistor open collector output points is a special block to control outputs of temperature inputs from thermocouples and platinum resistance thermometer bulbs by PID control Connect the FX2N 2LC to the FX1N FX2N FX2NC FX3U Series PLC 1 As input sensors two thermocouples two platinum resistance thermometer bulbs or one thermocouple and one platinum resistance thermometer bulb ...

Page 8: ... S E T B N PLII WRe5 26 U L JIS C 1602 1995 Resistance ther mometer bulb 3 wire Pt100 JIS C 1604 1997 JPt100 JIS C 1604 1981 Measurement precision Ambient temperature 23 C 5 C 0 3 of range span 1 digit Ambient temperature 0 C to 55 C 0 7 of range span 1 digit However 0 to 399 C 0 to 799 F in B inputs as well as 0 to 32 F in PLII and WRe5 26 inputs are outside precision guarantee range Cold contact...

Reviews: