background image

1..  Before installation or relocation

 Caution:

•  Be extremely careful when transporting the units. Two or more persons are 

needed to handle the unit, as it weighs 0 kg, 44 lbs or more. Do not grasp 

the packaging bands. Wear protective gloves as you can injure your hands 

on the fins or other parts.

•  Be sure to safely dispose of the packaging materials. Packaging materials, such 

as nails and other metal or wooden parts may cause stabs or other injuries.

•  Thermal insulation of the refrigerant pipe is necessary to prevent condensation. 

If the refrigerant pipe is not properly insulated, condensation will be formed.

Contents

 Warning:

•  Ask a dealer or an authorized technician to install the unit.

•  For installation work, follow the instructions in the Installation Manual and use 

tools and pipe components specifically made for use with refrigerant specified 

in the outdoor unit installation manual.

•  The unit must be installed according to the instructions in order to minimize 

the risk of damage from earthquakes, typhoons, or strong winds. An incor-

rectly installed unit may fall down and cause damage or injuries.

•  The unit must be securely installed on a structure that can sustain its weight. 

•  If the air conditioner is installed in a small room, measures must be taken to prevent 

the refrigerant concentration in the room from exceeding the safety limit in the 

event of refrigerant leakage. Should the refrigerant leak and cause the concentra-

tion limit to be exceeded, hazards due to lack of oxygen in the room may result.

•  Ventilate the room if refrigerant leaks during operation. If refrigerant comes 

into contact with a flame, poisonous gases will be released.

•  All electric work must be performed by a qualified technician according to 

local regulations and the instructions given in this manual. 

•  Use only specified cables for wiring.

•  The terminal block cover panel of the unit must be firmly attached.

•  Use only accessories authorized by Mitsubishi Electric and ask a dealer or 

an authorized technician to install them.

•  The user should never attempt to repair the unit or transfer it to another location.

•  After installation has been completed, check for refrigerant leaks. If refriger-

ant leaks into the room and comes into contact with the flame of a heater or 

portable cooking range, poisonous gases will be released.

•  When installing or relocating, or servicing the air conditioner, use only the 

specified refrigerant (R410A) to charge the refrigerant lines. Do not mix it with 

any other refrigerant and do not allow air to remain in the lines. 

  If air is mixed with the refrigerant, then it can be the cause of abnormal high 

pressure in the refrigerant line, and may result in an explosion and other 

hazards. 

  The use of any refrigerant other than that specified for the system will cause 

mechanical failure or system malfunction or unit breakdown. In the worst 

case, this could lead to a serious impediment to securing product safety. 

1.1.  Before installation (Environment)

 Caution:

•  Do not use the unit in an unusual environment. If the air conditioner is installed 

in areas exposed to steam, volatile oil (including machine oil), or sulfuric gas, 

areas exposed to high salt content such as the seaside, the performance can 

be significantly reduced and the internal parts can be damaged.

•  Do not install the unit where combustible gases may leak, be produced, flow, 

or accumulate. If combustible gas accumulates around the unit, fire or explo

-

sion may result.

•  Do not keep food, plants, caged pets, artwork, or precision instruments in the 

direct airflow of the indoor unit or too close to the unit, as these items can be 

damaged by temperature changes or dripping water.

•  When  the  room  humidity  exceeds  80%  or  when  the  drainpipe  is  clogged, 

water may drip from the indoor unit. Do not install the indoor unit where such 

dripping can cause damage.

•  When installing the unit in a hospital or communications office, be prepared for 

noise and electronic interference. Inverters, home appliances, high-frequency 

medical equipment, and radio communications equipment can cause the air 

conditioner to malfunction or breakdown. The air conditioner may also affect 

medical equipment, disturbing medical care, and communications equipment, 

harming the screen display quality.

•  Place thermal insulation on the pipes to prevent condensation. If the drain-

pipe is installed incorrectly, water leakage and damage to the ceiling, floor, 

furniture, or other possessions may result.

•  Do not clean the air conditioner unit with water. Electric shock may result.

•  Tighten all flare nuts to specification using a torque wrench. If tightened too 

much, the flare nut can break after an extended period.

1.3.  Before electric work

 Caution:

•  Be sure to install circuit breakers. If not installed, electric shock may result.

•  For the power lines, use standard cables of sufficient capacity. Otherwise, a 

short circuit, overheating, or fire may result.

•  When installing the power lines, do not apply tension to the cables.

•  Be sure to ground the unit. If the unit is not properly grounded, electric shock 

may result.

•  Use circuit breakers (ground fault interrupter, isolating switch (+B fuse), and 

molded case circuit breaker) with the specified capacity. If the circuit breaker 

capacity is larger than the specified capacity, breakdown or fire may result.

1.  Safety precautions .....................................................................................2

2.  Installation location ....................................................................................2

3.  Installing the indoor unit ............................................................................3

4.  Refrigerant pipe and drain pipe .................................................................4

5.  Electrical work ...........................................................................................6

6.  Test run ....................................................................................................10

7.  Installing the grille ....................................................................................10

1.  Safety precautions

1.4.  Before starting the test run

 Caution:

•  Turn on the main power switch more than 1 hours before starting operation. 

Starting operation just after turning on the power switch can severely damage 

the internal parts.

•  Before starting operation, check that all panels, guards and other protective parts 

are correctly installed. Rotating, hot, or high voltage parts can cause injuries.

•  Do not operate the air conditioner without the air filter set in place. If the air 

filter is not installed, dust may accumulate and breakdown may result.

•  Do not touch any switch with wet hands. Electric shock may result.

•  Do not touch the refrigerant pipes with bare hands during operation.

•  After stopping operation, be sure to wait at least five minutes before turning off 

the main power switch. Otherwise, water leakage or breakdown may result.

  Before installing the unit, make sure you read all the “Safety precau-

tions”.

  Please report to your supply authority or obtain their consent before 

connecting this equipment to the power supply system. 

 Warning:

Describes precautions that must be observed to prevent danger of injury or 

death to the user.

 Caution:

Describes precautions that must be observed to prevent damage to the unit.

After installation work has been completed, explain the “Safety precautions,” use, and 

maintenance of the unit to the customer according to the information in the Operation 

Manual and perform the test run to ensure normal operation. Both the Installation 

Manual and Operation Manual must be given to the user for keeping. These manuals 

must be passed on to subsequent users.

 : Indicates a part which must be grounded.

 Warning:

Carefully read the labels affixed to the main unit.

.  Installation location

Refer to the outdoor unit installation manual.

Note:

The phrase “Wired remote controller” in this installation manual refers to the PAR-21MAA.

If you need any information for the other remote controller, please refer to either the installation manual or initial setting manual which are included in these box.

Summary of Contents for City Multi Series PLFY-P08NCMU-E

Page 1: ...avant d installer ce climatiseur pour viter tout accident et vous assurer d une utilisation correcte MANUAL DE INSTALACI N Para un uso seguro y correcto lea detalladamente este manual de instalaci n a...

Page 2: ...ipping water When the room humidity exceeds 80 or when the drainpipe is clogged water may drip from the indoor unit Do not install the indoor unit where such dripping can cause damage When installing...

Page 3: ...nstallation template top of the package and the gauge supplied as an accessory with the grille make an opening in the ceiling so that the main unit can be installed as shown in the diagram The method...

Page 4: ...nto the suspension bolts in the order of the washers with insulation washers without insulation and nuts double Fit the washer with cushion so that the insulation faces downward In case of using upper...

Page 5: ...at surface Copper pipe O D mm inch Flare dimensions A dimensions mm inch 6 35 1 4 8 7 9 1 11 32 23 64 9 52 3 8 12 8 13 2 1 2 33 64 12 7 1 2 16 2 16 6 41 64 21 32 15 88 5 8 19 3 19 7 49 64 25 32 19 05...

Page 6: ...it B Insulating material C Band large D Drain port transparent E Insertion margin F Matching G Drain pipe O D 32 mm 1 1 4 inch PVC TUBE H Insulating material purchased locally I Transparent PVC pipe J...

Page 7: ...6 2 4 Type 2 PEFY NMAU 38 1 6 Type 3 PEFY NMHSU 13 8 4 8 Others Other indoor unit 0 0 C Multiple of tripping current at tripping time 0 01s Please pick up C from the tripping characteristic of the br...

Page 8: ...mote controller When installing wireless signal receiver Connect the wire of wireless signal receiver 9 pole cable to CN90 of indoor con troller board When more than two units are run under group cont...

Page 9: ...ad the remote controller cord from the back of the controller B 2 To run the remote controller cord through the upper portion 3 For direct installation on the wall C Wall D Conduit E Lock nut F Bushin...

Page 10: ...mp end 1 3 16 to 2 in B Cover of water supply inlet C About 1000 cc 1 4 gal D Water E Drain plug Fig 6 2 Fig 7 1 1 4 5 2 3 7 Installing the grille 7 1 Check the grille accessories Fig 7 1 The grille s...

Page 11: ...er panel A Intake grille B Grille C Intake grille levers D Grille hook Fig 7 2 7 Installing the grille 7 3 Installing the grille Please pay attention because there is a restriction in the attachment p...

Page 12: ...m on and drop from the ceiling or the unit could malfunction Fig 7 9 A Button B Vane motor C Up down vanes D Connector 7 3 4 Wire connection Fig 7 8 Be sure to connect the unit to the connector white...

Page 13: ...13...

Page 14: ...ttes d eau peuvent tomber de l appareil int rieur Ne pas installer l appareil int rieur dans un endroit o ces gouttes peuvent provoquer des dommages Lors de l installation de l appareil dans un h pita...

Page 15: ...ma d installation dans le haut du colis et le gabarit fourni comme accessoire avec la grille pour cr er une ouverture dans le plafond de sorte pouvoir installer l appareil principal comme illustr sur...

Page 16: ...sion dans l ordre rondelles avec isolant rondelles sans isolant et crous double Placer la rondelle avec isolant de telle sorte que la partie isolante soit tourn e vers le bas En cas d utilisation de r...

Page 17: ...ique sur toute la surface d appui vas e Diam ext Tuyau en cuivre mm inch Dimensions vasement Dimensions A mm inch 6 35 1 4 8 7 9 1 11 32 23 64 9 52 3 8 12 8 13 2 1 2 33 64 12 7 1 2 16 2 16 6 41 64 21...

Page 18: ...ati re isolante C Courroie grands D Port de drainage transparent E Marge d insertion F Correspondance G Tuyau de drainage Tuyau en PVC D E 32 mm 1 1 4 inch H Mati re isolante se procurer sur place I T...

Page 19: ...2 4 Type 2 PEFY NMAU 38 1 6 Type 3 PEFY NMHSU 13 8 4 8 Autres Autre appareil int rieur 0 0 C Courants d ouverture l ouverture 0 01 s S lectionnez C partir des caract ristiques d ouverture du disjoncte...

Page 20: ...eur de signaux sans fil Relier le fil du r cepteur de signaux sans fil c ble 9 p les au connecteur CN90 du bornier du contr leur int rieur Lorsque plus de deux appareils sont utilis s dans le cadre d...

Page 21: ...ri re la t l com mande B 2 Pour faire passer le cordon de la t l comamnde travers la partie sup rieure 3 Pour l installer directement au mur C Mur D Conduit E Contre crou F Manchon G Bo te de commutat...

Page 22: ...change 6 V rifier le bon fonctionnement du ventilateur de l appareil ext rieur 7 Arr ter l essai de fonctionnement en appuyant sur la touche ON OFF Marche Ar r t Arr t 8 Enregistrez un num ro de t l p...

Page 23: ...ochet de la grille Fig 7 2 7 Installer la grille 7 3 Installer la grille Faire tr s attention aux restrictions concernant la position de fixation de la grille 7 3 1 Pr paratifs Fig 7 5 Installer les d...

Page 24: ...ers le bas au del de la plage indiqu e De la condensation pourrait appara tre et provoquer l apparition de gouttes au plafond ou l appareil risquerait de mal fonctionner 7 5 Installation de la grille...

Page 25: ...25...

Page 26: ...idad interior en lugares donde el goteo pueda causar da os Si instala la unidad en un hospital o en un centro de comunicaciones re cuerde que la unidad produce ruidos e interferencias electr nicas Los...

Page 27: ...n parte superior del paquete y el calibre sumi nistrado como un accesorio junto a la rejilla realice una apertura en el techo de forma que la unidad principal se pueda instalar tal y como se indica en...

Page 28: ...dobles Coloque la arandela con el acolchado de forma que el aislamiento mire hacia abajo Si se utilizan arandelas superiores para colgar la unidad principal las arandelas inferiores con aislamiento y...

Page 29: ...a superficie abocardada Tubo de cobre O D mm inch Dimensiones de abocinado dimensiones A mm inch 6 35 1 4 8 7 9 1 11 32 23 64 9 52 3 8 12 8 13 2 1 2 33 64 12 7 1 2 16 2 16 6 41 64 21 32 15 88 5 8 19 3...

Page 30: ...ce VP25 tubo de PVC de 32 mm 1 1 4 inch para el tubo de drenaje y prevea una pendiente de descenso de 1 100 o m s Aseg rese de conectar las juntas de los tubos con un adhesivo de tipo polivinilo Obser...

Page 31: ...er ser compatible con el circuito del inversor El interruptor de fuga a tierra deber combinarse mediante un conmutador local o un interruptor de cableado 2 Tome el F1 o el F2 m s grande como valor par...

Page 32: ...de se ales inal mbricas cable de 9 polos a CN90 en el cuadro de control interior Si hay m s de dos unidades funcionando bajo el control de grupo utilizando el controlador remoto inal mbrico conecte ca...

Page 33: ...o por detr s del control B 2 Para pasar el cable del control remoto por la parte de arriba 3 Para instalarla en la pared C Pared D Conducto E Tuerca de seguridad F Casquillo 2 Procedimientos de conexi...

Page 34: ...locidad del aire Compruebe que cambia la velocidad del aire 6 Compruebe el funcionamiento del ventilador de la unidad exterior 7 Desactive la prueba de funcionamiento pulsando el bot n de activaci n d...

Page 35: ...D Gancho de la rejilla Fig 7 2 7 Instalaci n de la rejilla 7 3 Instalaci n de la rejilla Preste especial atenci n debido a la restricci n existente en la colocaci n de la posici n de la rejilla 7 3 1...

Page 36: ...ecificado Se podr a formar condensaci n y gotear desde el techo o podr a producrise un funcionamiento incorrecto de la unidad Fig 7 9 A Bot n B Motor de la paleta C Paletas de ascenso descenso D Conec...

Page 37: ...37...

Page 38: ...n this manual before handing it to the customer This product is designed and intended for use in the residential commercial and light industrial environment Printed in Thailand BH79D034H04 HEAD OFFICE...