6.  Test run

6.1.  Before test run

  After completing installation and the wiring and piping of the indoor and 

outdoor units, check for refrigerant leakage, looseness in the power supply 

or control wiring, wrong polarity, and no disconnection of one phase in the 

supply.

  Use a 500-volt megohmmeter to check that the resistance between the power 

supply terminals and ground is at least 1.0 M

.

  Do not carry out this test on the control wiring (low voltage circuit) termi

-

nals.

 Warning:

Do not use the air conditioner if the insulation resistance is less than 1.0 M

.

Fig. 6-1

A

 ON/OFF button

B

 Test run display

C

 Indoor temperature liquid line 

temperature display

D

 ON/OFF lamp

E

 Power display

F

 Error code display

 

Test  run  remaining  time 
display

G

 Set temperature button

H

 Mode selection button

I

 Fan speed button

M

 TEST button

6.3.  Check of drainage (Fig. 6-2)

•  During the test run, ensure the water is being properly drained out and that no water 

is leaking from joints.

•  Always check this during installation even if the unit is not required to provide cool-

ing/drying at that time.

• 

Similarly, check the drainage before finishing ceiling installation in a new premises.

(1) Remove the cover of the water supply inlet and add about 1000 cc, 1/4 gal. of 

water using a water supply pump etc. During this process, be careful not to spray 

water into the drain pump mechanism.

(2) Confirm that water is being drained out through the drainage outlet, after switching 

over from remote control mode to test run mode.

(3) After checking the drainage, ensure that the cover is replaced and the power 

supply is isolated.

(4) After confirming the drainage system is functioning, replace the drain plug.

A

 Insert the pump end 1-3/16 to 2 in.

B

 Cover of water supply inlet

C

 About 1000 cc, 1/4 gal.

D

 Water

E

 Drain plug

Fig. 6-

Fig. 7-1

1

4

5

2

3

7.  Installing the grille

7.1.  Check the grille accessories (Fig. 7-1)

•  The grille should be supplied with the following accessories.

Accessory name

Q’ty

Remark

1

Grille

1

650 

×

 650 mm, 25-19/32 

×

 25-19/32 inch

2

Screw with washer

4

M5 

×

 0.8 

×

 25

3

Gauge

1

4

Fastener

2

5

Band

2

6.2.  Test run (Fig. 6-1)

The following 3 methods are available.

1

  Turn on the power at least 12 hours before the test run.

2

  Press the [TEST] button twice. 

 “TEST RUN” liquid crystal display

3

  Press the [Mode selection] button. 

 Make sure that wind is blown out.

4

  Press the [Mode selection] button and switch to the cooling (or heating) mode. 

 

 Make sure that cold (or warm) wind is blown out.

5

  Press the [Fan speed] button. 

 Make sure that the wind speed is switched.

6

  Check operation of the outdoor unit fan.

7

  Release test run by pressing the [ON/OFF] button. 

 Stop

8

  Register a telephone number.

  The telephone number of the repair shop, sales office, etc., to contact if an error 

occurs can be registered in the remote controller. The telephone number will be 

displayed when an error occurs. For registration procedures, refer to the operation 

manual for the indoor unit.

Note:

•  If an error code is displayed on the remote controller or if the air conditioner 

does not operate properly, refer to the outdoor unit installation manual or 

other technical materials.

•  The OFF timer is set for the test run to automatically stop after 2 hours.

•  During the test run, the time remaining is shown in the time display.

•  During the test run, the temperature of the indoor unit refrigerant pipes is 

shown in the room temperature display of the remote controller.

•  When the VANE or LOUVER button is pressed, the message “NOT AVAILABLE” 

may appear on the remote controller display depending on the indoor unit 

model, but this is not a malfunction.

Summary of Contents for City Multi Series PLFY-P08NCMU-E

Page 1: ...avant d installer ce climatiseur pour viter tout accident et vous assurer d une utilisation correcte MANUAL DE INSTALACI N Para un uso seguro y correcto lea detalladamente este manual de instalaci n a...

Page 2: ...ipping water When the room humidity exceeds 80 or when the drainpipe is clogged water may drip from the indoor unit Do not install the indoor unit where such dripping can cause damage When installing...

Page 3: ...nstallation template top of the package and the gauge supplied as an accessory with the grille make an opening in the ceiling so that the main unit can be installed as shown in the diagram The method...

Page 4: ...nto the suspension bolts in the order of the washers with insulation washers without insulation and nuts double Fit the washer with cushion so that the insulation faces downward In case of using upper...

Page 5: ...at surface Copper pipe O D mm inch Flare dimensions A dimensions mm inch 6 35 1 4 8 7 9 1 11 32 23 64 9 52 3 8 12 8 13 2 1 2 33 64 12 7 1 2 16 2 16 6 41 64 21 32 15 88 5 8 19 3 19 7 49 64 25 32 19 05...

Page 6: ...it B Insulating material C Band large D Drain port transparent E Insertion margin F Matching G Drain pipe O D 32 mm 1 1 4 inch PVC TUBE H Insulating material purchased locally I Transparent PVC pipe J...

Page 7: ...6 2 4 Type 2 PEFY NMAU 38 1 6 Type 3 PEFY NMHSU 13 8 4 8 Others Other indoor unit 0 0 C Multiple of tripping current at tripping time 0 01s Please pick up C from the tripping characteristic of the br...

Page 8: ...mote controller When installing wireless signal receiver Connect the wire of wireless signal receiver 9 pole cable to CN90 of indoor con troller board When more than two units are run under group cont...

Page 9: ...ad the remote controller cord from the back of the controller B 2 To run the remote controller cord through the upper portion 3 For direct installation on the wall C Wall D Conduit E Lock nut F Bushin...

Page 10: ...mp end 1 3 16 to 2 in B Cover of water supply inlet C About 1000 cc 1 4 gal D Water E Drain plug Fig 6 2 Fig 7 1 1 4 5 2 3 7 Installing the grille 7 1 Check the grille accessories Fig 7 1 The grille s...

Page 11: ...er panel A Intake grille B Grille C Intake grille levers D Grille hook Fig 7 2 7 Installing the grille 7 3 Installing the grille Please pay attention because there is a restriction in the attachment p...

Page 12: ...m on and drop from the ceiling or the unit could malfunction Fig 7 9 A Button B Vane motor C Up down vanes D Connector 7 3 4 Wire connection Fig 7 8 Be sure to connect the unit to the connector white...

Page 13: ...13...

Page 14: ...ttes d eau peuvent tomber de l appareil int rieur Ne pas installer l appareil int rieur dans un endroit o ces gouttes peuvent provoquer des dommages Lors de l installation de l appareil dans un h pita...

Page 15: ...ma d installation dans le haut du colis et le gabarit fourni comme accessoire avec la grille pour cr er une ouverture dans le plafond de sorte pouvoir installer l appareil principal comme illustr sur...

Page 16: ...sion dans l ordre rondelles avec isolant rondelles sans isolant et crous double Placer la rondelle avec isolant de telle sorte que la partie isolante soit tourn e vers le bas En cas d utilisation de r...

Page 17: ...ique sur toute la surface d appui vas e Diam ext Tuyau en cuivre mm inch Dimensions vasement Dimensions A mm inch 6 35 1 4 8 7 9 1 11 32 23 64 9 52 3 8 12 8 13 2 1 2 33 64 12 7 1 2 16 2 16 6 41 64 21...

Page 18: ...ati re isolante C Courroie grands D Port de drainage transparent E Marge d insertion F Correspondance G Tuyau de drainage Tuyau en PVC D E 32 mm 1 1 4 inch H Mati re isolante se procurer sur place I T...

Page 19: ...2 4 Type 2 PEFY NMAU 38 1 6 Type 3 PEFY NMHSU 13 8 4 8 Autres Autre appareil int rieur 0 0 C Courants d ouverture l ouverture 0 01 s S lectionnez C partir des caract ristiques d ouverture du disjoncte...

Page 20: ...eur de signaux sans fil Relier le fil du r cepteur de signaux sans fil c ble 9 p les au connecteur CN90 du bornier du contr leur int rieur Lorsque plus de deux appareils sont utilis s dans le cadre d...

Page 21: ...ri re la t l com mande B 2 Pour faire passer le cordon de la t l comamnde travers la partie sup rieure 3 Pour l installer directement au mur C Mur D Conduit E Contre crou F Manchon G Bo te de commutat...

Page 22: ...change 6 V rifier le bon fonctionnement du ventilateur de l appareil ext rieur 7 Arr ter l essai de fonctionnement en appuyant sur la touche ON OFF Marche Ar r t Arr t 8 Enregistrez un num ro de t l p...

Page 23: ...ochet de la grille Fig 7 2 7 Installer la grille 7 3 Installer la grille Faire tr s attention aux restrictions concernant la position de fixation de la grille 7 3 1 Pr paratifs Fig 7 5 Installer les d...

Page 24: ...ers le bas au del de la plage indiqu e De la condensation pourrait appara tre et provoquer l apparition de gouttes au plafond ou l appareil risquerait de mal fonctionner 7 5 Installation de la grille...

Page 25: ...25...

Page 26: ...idad interior en lugares donde el goteo pueda causar da os Si instala la unidad en un hospital o en un centro de comunicaciones re cuerde que la unidad produce ruidos e interferencias electr nicas Los...

Page 27: ...n parte superior del paquete y el calibre sumi nistrado como un accesorio junto a la rejilla realice una apertura en el techo de forma que la unidad principal se pueda instalar tal y como se indica en...

Page 28: ...dobles Coloque la arandela con el acolchado de forma que el aislamiento mire hacia abajo Si se utilizan arandelas superiores para colgar la unidad principal las arandelas inferiores con aislamiento y...

Page 29: ...a superficie abocardada Tubo de cobre O D mm inch Dimensiones de abocinado dimensiones A mm inch 6 35 1 4 8 7 9 1 11 32 23 64 9 52 3 8 12 8 13 2 1 2 33 64 12 7 1 2 16 2 16 6 41 64 21 32 15 88 5 8 19 3...

Page 30: ...ce VP25 tubo de PVC de 32 mm 1 1 4 inch para el tubo de drenaje y prevea una pendiente de descenso de 1 100 o m s Aseg rese de conectar las juntas de los tubos con un adhesivo de tipo polivinilo Obser...

Page 31: ...er ser compatible con el circuito del inversor El interruptor de fuga a tierra deber combinarse mediante un conmutador local o un interruptor de cableado 2 Tome el F1 o el F2 m s grande como valor par...

Page 32: ...de se ales inal mbricas cable de 9 polos a CN90 en el cuadro de control interior Si hay m s de dos unidades funcionando bajo el control de grupo utilizando el controlador remoto inal mbrico conecte ca...

Page 33: ...o por detr s del control B 2 Para pasar el cable del control remoto por la parte de arriba 3 Para instalarla en la pared C Pared D Conducto E Tuerca de seguridad F Casquillo 2 Procedimientos de conexi...

Page 34: ...locidad del aire Compruebe que cambia la velocidad del aire 6 Compruebe el funcionamiento del ventilador de la unidad exterior 7 Desactive la prueba de funcionamiento pulsando el bot n de activaci n d...

Page 35: ...D Gancho de la rejilla Fig 7 2 7 Instalaci n de la rejilla 7 3 Instalaci n de la rejilla Preste especial atenci n debido a la restricci n existente en la colocaci n de la posici n de la rejilla 7 3 1...

Page 36: ...ecificado Se podr a formar condensaci n y gotear desde el techo o podr a producrise un funcionamiento incorrecto de la unidad Fig 7 9 A Bot n B Motor de la paleta C Paletas de ascenso descenso D Conec...

Page 37: ...37...

Page 38: ...n this manual before handing it to the customer This product is designed and intended for use in the residential commercial and light industrial environment Printed in Thailand BH79D034H04 HEAD OFFICE...

Reviews: