en
47
WT09050X01
(3) When a transmission booster unit is connected
ME
IC
HB
M1M2 S
TB5
IC
M1M2 S
TB5
RP
A B
A B
A B
S
TB2
A B S
TB3
L
8
ME
IC
M1M2 S
TB5
IC
M1M2 S
TB5
M1M2 S
M1M2
TB3
M1M2 S
TB7
OC
(51)
Ⓐ
CN41
TB02
111
Ⓐ
Shielded cable
*1 Daisy-chain terminals (TB3) on outdoor units together in the same refrigerant system.
*2 Leave the power jumper connected to CN41.
Maximum allowable length of control cables
Transmission cables
L
1
+ L
2
+ L
3
+ L
4
, L
1
+ L
2
+ L
3
+ L
5
, L
6
+ L
7
, L
6
+ L
8
≤ 200 m (656 ft)
Remote controller cables
ℓ
1
, ℓ
2
≤ 10 m (32 ft)
* If the length exceeds 10 m (32 ft), the length that exceeds 10 m (32 ft) needs
to be included in the maximum allowable length of transmission cables
above.
Earth