53
WT09050X01
10-6. Address setting
・
Set the address setting switch as follows.
Address setting method
Address
Indoor unit (Main, Sub)
Assign the lowest address to the main indoor unit in the group, and assign sequential
addresses to the rest of the indoor units in the same group.
* In a system with a sub HBC controller, make the settings for the indoor units in the
following order. (Set the addresses so that the addresses of
①
are smaller than those of
②
.)
①
Indoor units that are connected to the main HBC controller
②
Indoor units that are connected to the sub HBC controller
01 to 50
Outdoor unit (OC)
Assign sequential addresses to the outdoor units in the same refrigerant system.
* To set the address to 100, the address setting switch must be set to 50.
51 to 100
HBC controller
Main
Assign an address that equals the address of the outdoor unit plus 1. If the address that
is assigned to the main HBC controller overlaps any of the addresses that are assigned
to the outdoor units or to the sub HBC controller, use a different, unused address within
the setting range.
* To set the address to 100, the address setting switch must be set to 50.
51 to 100
Sub
Assign an address that equals the lowest address of the indoor units that are connected
to the sub HBC controller plus 50.
* To set the address to 100, the address setting switch must be set to 50.
51 to 100
ME remote controller
Main
Assign an address that equals the address of the main indoor unit in the group plus 100.
101 to 150
Sub
Assign an address that equals the address of the main indoor unit in the group plus 150.
151 to 200
MA remote controller
Address setting is not required. (The Main/Sub setting is required.)
–
* Make indoor unit group settings from remote controllers after turning on the power to all units.
Address setting switch (Outdoor units)