background image

9

4.6.  Additional refrigerant charge

Refrigerant of 3 kg equivalent to 50 m total extended piping length is already included 
when the outdoor unit is shipped. Thus, if the total extended piping length is 50 m or 
less, there is no need to charge with additional refrigerant.

Calculation of Additional Refrigerant Charge

•  If the total extended piping length exceeds 50 m, calculate the required additional 

refrigerant charge using the procedure shown below.

•  If the calculated additional refrigerant charge is a negative amount, do not charge 

with any refrigerant.

<Additional Charge>

Additional  
refrigerant charge

=

Liquid pipe size 
Total length of
ø9.52 

×

 0.06

+

Liquid pipe size 
Total length of 
ø6.35 

×

 0.024

Refrigerant  
amount for 
outdoor unit

(kg)

(m) 

×

 0.06 (kg/m)

(m) 

×

 0.024 (kg/m)

3.0 kg

<Example>
Outdoor model  :  125
Indoor  1 :  63 

A :  ø9.52 

30 m 

a :  ø9.52 

15 m

 

2 :  40 

     

 

b :  ø6.35 

10 m

 3 

25 

 

 

   

ø6.35 

10 

m

 

4 :  20 

     

 

d :  ø6.35 

20 m

The total length of each liquid line is as follows
ø9.52 : A + a  = 30 + 15  = 45 m
ø6.35 : b + c + d = 10 + 10 + 20 = 40 m
Therefore,
<Calculation example>
Additional refrigerant charge 
= 45 

×

 0.06 + 40 

×

 0.024 – 3.0 = 0.7 kg (rounded up)

4.  Installing the refrigerant piping

5.  Drainage piping work

Outdoor unit drainage pipe connection

When drain piping is necessary, use the drain socket or the drain pan (option).

P100-140

Drain socket

PAC-SG61DS-E

Drain pan

PAC-SG64DP-E

6.1. Caution

1

  Follow ordinance of your governmental organization for technical standard related 

to electrical equipment, wiring regulations and guidance of each electric power 
company.

2

  Wiring for control (hereinafter referred to as transmission line) shall be (5 cm or 

more) apart from power source wiring so that it is not influenced by electric noise 
from power source wiring. (Do not insert transmission line and power source wire 
in the same conduit.)

3

  Be sure to provide designated grounding work to outdoor unit.

4

  Give some allowance to wiring for electrical part box of indoor and outdoor units, 

because the box is sometimes removed at the time of service work.

5

  Never connect the main power source to terminal block of transmission line. If 

connected, electrical parts will be burnt out.

6

  Use 2-core shield cable for transmission line. If transmission lines of different 

systems are wired with the same multiplecore cable, the resultant poor transmit-
ting and receiving will cause erroneous operations.

6. Electrical work

7

  Only the transmission line specified should be connected to the terminal block 

for outdoor unit transmission.

 

(Transmission line to be connected with indoor unit : Terminal block TB3 for 
transmission line, Other : Terminal block TB7 for centralized control)

 

Erroneous connection does not allow the system to operate.

8

  In case to connect with the upper class controller or to conduct group operation in 

different refrigerant systems, the control line for transmission is required between 
the outdoor units each other.

 

Connect this control line between the terminal blocks for centralized control. (2-
wire line with no polarity)

 

When conducting group operation in different refrigerant systems without connect-
ing to the upper class controller, replace the insertion of the short circuit connector 
from CN41 of one outdoor unit to CN40.

9

  Group is set by operating the remote controller.

At the conditions 

below:

*   The figure to the left is an example 

only. The stop valve shape, service port 
position, etc., may vary according to the 
model.

* Turn 

section 

A

 only.

 

(Do not further tighten sections 

A

 and 

B

 together. )

C

 Charge hose

D

  Service port

Precautions when using the charge valve (Fig.4-8)

Do not tighten the service port too much when installing it, otherwise, the valve core 
could be deformed and become loose, causing a gas leak.
After positioning section 

B

 in the desired direction, turn section 

A

 only and tighten 

it.
Do not further tighten sections 

A

 and 

B

 together after tightening section 

A

.

Fig. 4-8

Summary of Contents for CITY MULTI PUMY-P100YHMB

Page 1: ...INSTALACI N Para un uso correcto y seguro lea detalladamente este manual y el manual de instalaci n de la unidad interior antes de instalar la unidad de aire acondicionado MANUALE DI INSTALLAZIONE Per...

Page 2: ...result in an explosion and other hazards The use of any refrigerant other than that speci ed for the system will cause mechanical failure or system malfunction or unit breakdown In the worst case thi...

Page 3: ...rigeration oil oil deterioration may result Do not use refrigerant other than R410A refrigerant If another refrigerant is used the chlorine will cause the oil to deteriorate Use the following tools sp...

Page 4: ...unit within the outdoor unit s capacity if possible Only when all the indoor units are 1 5 kW models 12 indoor units can be connected to 1 outdoor unit 2 4 Connecting a PWFY Unit When using a PWFY uni...

Page 5: ...air outlet guides for upward air ow 2 5 2 When installing multiple outdoor units Leave 10 mm space or more between the units 1 Obstacles at rear only Fig 2 9 2 Obstacles at rear and above only Fig 2 1...

Page 6: ...le structure it may fall down and cause damage or injuries The unit must be installed according to the instructions in order to minimize the risk of damage from earthquakes typhoons or strong winds An...

Page 7: ...ealing is used refer to Table 3 for aring of R410A refrigerant pipes The size adjustment gauge can be used to con rm A measurements Warning When installing the unit securely connect the refrigerant pi...

Page 8: ...ure does not decrease 2 Pressurize to 1 5 MPa 15 kgf cm2 G wait ve minutes and make sure the pressure does not decrease 3 Pressurize to 4 15 MPa 41 5 kgf cm2 G and measure the surrounding tem perature...

Page 9: ...to outdoor unit 4 Give some allowance to wiring for electrical part box of indoor and outdoor units because the box is sometimes removed at the time of service work 5 Never connect the main power sour...

Page 10: ...the same group plus 100 M NET R C Sub 151 to 200 Set at an IC Main address within the same group plus 150 MA R C Unnecessary address setting Necessary main sub setting h The group setting operations a...

Page 11: ...r If no earth leakage breaker is installed it may cause an electric shock Do not use anything other than breaker and fuse with correct capacity Using fuse and wire or copper wire with too large capaci...

Page 12: ...carry out pump down operation if the amount of refrigerant inside the indoor unit is larger than the amount of charge less refrigerant Carrying out a pump down operation when the amount of refrigerant...

Page 13: ...123 1 123 2 125 3 127 4 127 5 130 6 130 7 133 S TB3 TB7 6 2 R410A R410A HFC 1 6 R410A C1220 R410A Mitsubishi Electric 1 10 2002 96 IV R410A R410A GWP 1975...

Page 14: ...124 1 1 1 1 2 20 1 3 1 4 12 B 1 5 R410A C1220 127 R22 127 R410A R410A R410A R410A...

Page 15: ...5 12 1 2 4 PWFY PWFY PWFY 2 4 1 1 PWFY P100VM E AU PWFY P200VM E AU PWFY P100VM E BU PWFY PWFY 50 100 PWFY PUMY P100 1 PWFY 5 6 11 2 PUMY P125 1 PWFY 7 1 14 0 PUMY P140 1 PWFY 8 0 15 5 2 4 2 PWFY PUM...

Page 16: ...300 200 1000 150 1000 300 1500 1500 500 1000 600 2000 150 1500 600 3000 500 1500 800 150 2 5 2 5 1 1 Fig 2 3 2 Fig 2 4 3 Fig 2 5 4 Fig 2 6 500 5 Fig 2 7 500 6 Fig 2 8 2 5 2 10 1 Fig 2 9 2 Fig 2 10 3 F...

Page 17: ...A 2 Fig 2 17 B Fig 2 16 Fig 2 17 2 Fig 3 1 4 4 1 R410A 124 R410A C1220 R410A 15 50 63 140 6 35 0 8 9 52 0 8 12 7 0 8 15 88 1 0 3 Fig 3 1 M10 3 8 120 70 320 30 10 5 15 A 10 3 8 B C D 30 600 600 360 10...

Page 18: ...D a b c d e 120 L A B C D e 80 B C D e 30 H 50 20 h 12 A a b c d e f 120 L A f 80 f 30 H 50 20 h 12 Fig 4 1 A B A B 3 Fig 4 3 A Fig 4 2 B Fig 4 2 O D A R410A R22 R407C 6 35 0 0 5 1 0 1 5 9 52 0 0 5 1...

Page 19: ...1 2 4 3 Fig 4 4 D A B 1 2 3 4 4 4 20 25 200 250 5 4 4 1 A B C A B 2 1 0 5 5 2 G 2 1 5 15 2 G 3 4 15 41 5 2 G 3 1 C 0 01 0 1 2 G 4 2 3 4 5 1 Fig 4 6 1 1 4 2 2 Fig 4 7 1 4 6 35 4 5 9 52 10 2 A B C D E F...

Page 20: ...35 10 3 25 c 6 35 10 4 20 d 6 35 20 9 52 A a 30 15 45 6 35 b c d 10 10 20 40 45 0 06 40 0 024 3 0 0 7 5 6 1 1 C 2 5 3 4 5 6 2 6 7 3 7 8 2 CN41 CN40 9 3 0 6 35 0 024 0 024 9 52 0 06 0 06 A A B C D Fig...

Page 21: ...L6 L2 L6 L7 200 1 25 2 1 2 2 3 4 10 0 5 1 25 2 10 1 25 2 L8 2 MA M NET L1 L2 L3 L4 L1 L2 L6 L7 500 1 25 2 M NET L1 L3 L4 L6 L2 L6 L7 200 1 25 2 m1 m1 m2 m3 m1 m2 m3 m4 200 0 3 1 25 2 6 2 Fig 6 1 1 TB3...

Page 22: ...1 A B A B A B A B M1M2 S TB3 M1M2S TB7 IC 51 M1M2 1 2 S TB5 TB15 1 2 TB15 1 2 TB15 1 2 TB15 1 2 TB15 1 2 TB15 1 2 TB15 MA 01 IC M1M2S TB5 03 IC M1M2S TB5 02 IC M1M2S TB5 04 IC M1M2S TB5 05 IC M1M2S T...

Page 23: ...SW3 7 2 1 SW3 1 OFF DIP SW3 2 DIP SW3 1 DIP SW3 1 7 3 1 COOL TEST RUN 2 3 SW3 2 OFF SW3 1 ON 4 SW2 4 OFF ON 5 ON 6 0 0 1 0 1 2 5 SW3 1 OFF 7 SW2 4 ON OFF 8 1 2 SW2 4 ON OFF 3 SW3 1 ON SW3 2 ON OFF 4...

Page 24: ...XBRIDGE MIDDLESEX UB8 1QQ UK Please be sure to put the contact address telephone number on this manual before handing it to the customer This product is designed and intended for use in the residentia...

Reviews: