3
2. SYSTEM CONFIGURATION
2.1 Total configuration
The total configuration employed when the AJ65SBT-RPS/RPG module is
used is as shown below.
Remote I/O
station
Master station
Remote
device station
Local station
Intelligent
device station
Repeater
(AJ65SBT-RPS/RPG)
CC-Link dedicated cable
Termination resistor (required)
[Segment]
Fiber-optic cable
*1
*2
Repeater
(AJ65SBT-RPS/RPG)
Remote I/O
station
Repeater
(AJ65SBT-RPS/RPG)
[Segment (1st stage)]
[Segment (1st stage)]
[Segment (2nd stage)]
Intelligent
device station
Remote
device station
Remote I/O
station
Repeater
(AJ65SBT-RPS/RPG)
Repeater
(AJ65SBT-RPS/RPG)
Remote I/O station
Remote I/O station
*1 The transmission speed of each segment must be matched with that of the master station.
*2 Up to 3 stages of segments may be used. (Up to 2 stages when the AJ65SBT-RPGs are used)
(1) What is a repeater?
This is the module for expanding the CC-Link system by connecting the
segments to each other.
(2) What is a segment?
In the CC-Link system where repeaters are used, the equipment included
between terminating resistances connected to each other through cross-
over cables is generally called the segment.