16
(4) When installing the AJ65SBT-RPS/RPG module on the control panel, to
improve the ventilation and facilitate the replacement of the module, provide
a distance of 60 mm (2.36inch) or longer between the upper and lower
surfaces of the module and the structural members or parts.
(5) Install the AJ65SBT-RPS/RPG module on a flat smooth surface.
If there are irregularities on the installation surface, undue force may be
applied to the printed circuit boards, and the boards may be damaged.
(6) Depending on the grounding condition of the system, a high-frequency
noise may occur between the systems. When these systems are connected
through CC-Link communication cables, a communication error may occur
by the mixing of noise into the repeaters.
If the high-frequency noise occurs between the systems connected through
the cables of 10 m (32.79ft.) or shorter, take the measure which uses CC-
Link cables of 10 m (32.79ft.) or longer between the systems.
Remote
station
Repeater
(AJ65SBT-RPS/RPG)
[System 1]
Remote
station
[System 2 (Control panel which may produce noise)]
10 m
(37.79ft.)
or shorter
Source of high-frequency
noise (servo, inverter)
Method : Use the cables of 10 m
(37.79ft.)or longer.
4.2.2 Installation environment
For the installation environment, refer to the User's Manual of the applicable
small type remote I/O module.