5 - 5
MELSEC-A
5 PROGRAMMING
(2) Initial setting by remote device station initialization procedure
registration
(a) Setting the target station number
Set the station number to which initial setting will be made.
Set the target station number to "1".
(b) Setting the procedure registration
When the initial data processing request flag (RX18) turns on and the
remote device station initialization procedure registration (SB0D) is set, the
following data are registered to the AJ65SBT-64AD.
Procedure Execution Condition
Execution
A/D conversion enable/prohibit specification: channels 1, 2: enable
(RWw0: 0003
H
)
Input range setting : channel 1: 0 to 5V
: channel 2: user range setting 1
(RWw1: 51
H
)
Moving average processing count setting: channel 2: 16 times
(RWw5: 10
H
)
CH.1 moving average processing specifying flag: sampling processing
(RY00:OFF)
CH.2 moving average processing specifying flag: moving average processing
(RY01:ON)
Initial data processing completion flag (RY18) is turned on.
Initial data processing request flag (RX18) turns on
Initial data setting request flag (RY19) is turned on.
Initial data processing request flag (RX18) turns off
Initial data processing completion flag (RY18) is turned off.
Initial data setting completion flag (RX19) turns on
Initial data setting request flag (RY19) is turned off.
(c) Setting results
The setting results are shown below.