3 - 14
MELSEC-A
3 SPECIFICATION
3.6.2 A/D conversion enable/prohibit specification (Address RWwm)
(1) Set whether A/D conversion is enabled or disabled per channel.
(2) By setting the unused channels to conversion prohibit, the sampling cycle can be
shortened.
Example) The sampling cycle when only channels 1 and 3 are set to A/D
conversion enabled:
2 (Number of channels enabled) × 1ms (Conversion speed at one channel) = 2ms
(3) Operation is performed according to the setting made for the leading edges of
initial data setting request flag (RY(n+1)9).
(4) The default setting is A/D conversion disable for all channels.
b15
b14
b13
b12
b11
b10
b9
b8
b7
b6
b5
b4
b3
b2
b1
CH.2 CH.1
b0
Ignored
CH.3
CH.4
1: Enable A/D conversion
0: Prohibit A/D conversion
Summary of Contents for AJ65SBT-64AD
Page 2: ......
Page 13: ...1 2 MELSEC A 1 OVERVIEW MEMO 1...
Page 69: ...Index 3 MEMO...
Page 71: ......