34
4.3.2 Part names and settings of Power Supply Module
The part names of the power supply modules are explained below.
(1) Part names of the A61RP module
Module fixing hooks
Hook for fixing module in the base unit.
5VDC power display LED for "DC", 100/200VAC input power
display LED for "AC"
Power fuse, fuse holder
4A cartridge fuse for AC input power is secured by the fuse holdr.
Spare fuse for power supply, mounted on rear side of the
terminal cover.
For details, see below. (Located under the terminal cover.)
Allows the module to be secured with a screw in addition to the
module fixing hook. (For M4 screws)
100VAC or 200VAC alternating current is connected using
the power supply input terminal.
Terminals for selecting applied voltage. Use 100 VAC or 200
VAC as described below. When 100 VAC is input, connect
together the "SHORT AC100V" terminals with the jumper
provided. When 200 VAC is input, connect together the
"SHORT AC200V" terminals with the jumper provided.
Grounding of power filter. Has half the input potential.
Connetion terminal conected to the shielding pattern on printed
circuit board.
M4 x 0.7 x 6
"POWER"LED
Spare fuse for power supply
Terminal block
Terminal cover
Module mounting screw installation holes
Power input terminal
LG terminal
FG terminal
Terinal screw
External output terminal
Applied voltage select terminals
Terminal details
Cover for protection of terminal block. Remove during wiring.
Re-install after wiring.
The external output terminals provide external contact output
(open contact) when:
The 5VDC output falls to or below 4.6VDC;
The 5VDC output is shorted;
The POWER LED goes off; or
The CPU module generates a stop error.*
REMARK
*: Check the CPU operating status in the troubleshooting/error code list of
the Q4ARCPU User's Manual.