232
6105
• An error (e.g. retry limit exceeded)
occurred in tracking (data
transmission).
(This error may be caused by tracking
cable removal or other system power-
off (including reset).)
• The error occurred at a startup since
the redundant system startup
procedure was not followed.
(This can be detected from the control
system or standby system of the
redundant system.)
• Check the CPU module or tracking
cable. If the error still occurs, this
indicates the CPU module or tracking
cable is faulty. (Contact your local
Mitsubishi representative, explaining
a detailed description of the problem.)
• Confirm the redundant system startup
procedure, and execute a startup
again.
QnPRH
6106
• A timeout error occurred in tracking
(data transmission).
(This error may be caused by tracking
cable removal or other system power-
off (including reset).)
• The error occurred at a startup since
the redundant system startup
procedure was not followed.
(This can be detected from the control
system or standby system of the
redundant system.)
6107
A data sum value error occurred in
tracking (data reception).
(This can be detected from the control
system or standby system of the
redundant system.)
• Check the CPU module or tracking
cable. If the error still occurs, this
indicates the CPU module or tracking
cable is faulty. (Contact your local
Mitsubishi representative, explaining
a detailed description of the problem.)
• Confirm the redundant system startup
procedure, and execute a startup
again.
QnPRH
6108
• A data error (other than sum value
error) occurred in tracking (data
reception).
(This error may be caused by tracking
cable removal or other system power-
off (including reset).)
• The error occurred at a startup since
the redundant system startup
procedure was not followed.
(This can be detected from the control
system or standby system of the
redundant system.)
6110
The tracking capacity exceeded the
allowed range.
(This can be detected from the control
system or standby system of the
redundant system.)
Reexamine the tracking capacity.
QnPRH
Error
Code
(SD0)
Error Contents and Cause
Corrective Action
Corresponding
CPU
*1
The module whose first 5 digits of serial No. is 09012 or later.
Summary of Contents for 13J851
Page 2: ......
Page 95: ...82 MEMO...
Page 101: ...88 MEMO...
Page 268: ...255 MEMO...
Page 269: ......