152
2200
There is no parameter file in the drive
specified as valid parameter drive by
the DIP switches.
• Check and correct the valid
parameter drive settings made by the
DIP switches.
• Set the parameter file to the drive
specified as valid parameter drive by
the DIP switches.
Qn(H)
QnPH
QnPRH
There is no parameter file at the
program memory.
Set the parameter file to the program
memory.
Q00J/Q00/Q01
Parameter file does not exist in all
drives where parameters will be valid.
Set a parameter file in a drive to be
valid.
QuU
2210
The contents of the boot file are
incorrect.
Check the boot setting.
Q00J/Q00/
Q01
*3
Qn(H)
QnPH
QnPRH
QnU
There is no boot file in the drive
designated by the parameter enabled
drive switch even though the Boot DIP
switch is ON.
Check and correct the valid parameter
drive settings made by the DIP
switches.
Set the boot file to the drive specified by
the parameter drive DIP switches.
QnA
2211
File formatting is failed at a boot.
• Reboot.
• CPU module hardware fault. (Contact
your local Mitsubishi representative,
explaining a detailed description of
the problem.)
Qn(H)
QnPRH
QnU
Error
Code
(SD0)
Error Contents and Cause
Corrective Action
Corresponding
CPU
*3
The function version is B or later.
*4
The function version is A.
*5
The module whose first 5 digits of serial No. is 04101 or later.
*6
The module whose first 5 digits of serial No. is 09012 or later.
*7
The Universal model QCPU except the Q02UCPU.