Refrigeration cycle system protection
(i) Starting conditions
1)
2)
When 5 minutes have elapsed after the compressor ON or the completion of the defrost control
Other than the defrost control
(ii) Contents of control
1)
(iii) Resetting condition
When the compressor has been turned OFF
2)
When the conditions of (i) above are met, the compressor stops.
Error stop occurs when the compressor has stopped 3 times within 60 minutes.
3)
When, after meeting the conditions of 1) and 2) above, the compressor speed, indoor temperature (Thi) and indoor
heat exchanger temperature (Th2) have met the conditions in the following table for 5 minutes:
Note (1) Except that the fan speed is HI in heating operation.
Compressor speed (N)
Operation mode
Cooling
Heating
(1)
Indoor temperature (Th1)
Th1−4<Th2
Indoor temperature (Th1)/
Indoor heat exchanger temperature (Th2)
Th2<Th1+6
50 N
<
=
10 Th1 40
<
=
<
=
0 Th1 40
<
=
<
=
50 N
<
=