(11-3) Check that the daily report data is sent/received. (Only for remote terminal communication)
①
From the [MY SITES] screen, click [DETAILS] of the building where the gateway is installed this time.
②
Pull-down [Other unit info], and click [Transfer request].
③
Press the [REQUEST] button.
④
Execute step
①
again. Then pull-down [Other unit info], and click [Daily report data].
⑤
Check whether the daily report data from midnight to the present time of the same day is displayed
in the [Other] field. It may take 10 minutes for the daily report data to be displayed depending on the
radio wave conditions.