130
-
'19 • KT-T-310D
PJG000Z312
(kW)
15
℃
WB
20
℃
WB
25
℃
WB
28
℃
WB
30
℃
WB
32
℃
WB
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
20
℃
DB
6.39
6.39
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
25
℃
DB
6.39
6.39
9.04
5.41
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
30
℃
DB
8.84
8.84
8.98
8.29 16.72 6.65 22.00 5.49
0.00
0.00
0.00
0.00
35
℃
DB
11.19 11.19 11.21 11.21 16.46 9.44 21.69 8.28 25.44 7.42 29.42 6.48
40
℃
DB
13.36 13.36 13.38 13.38 16.00 12.11 20.99 10.90 24.56 10.01 28.35 9.05
20
℃
DB
6.68
6.68
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
25
℃
DB
6.68
6.68
9.41
5.66
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
30
℃
DB
9.24
9.24
9.34
8.66 17.39 6.92 22.88 5.68
0.00
0.00
0.00
0.00
35
℃
DB
11.70 11.70 11.71 11.71 17.12 9.87 22.56 8.61 26.33 7.72 30.44 6.71
40
℃
DB
13.97 13.97 13.98 13.98 16.64 12.65 21.72 11.39 25.42 10.41 29.34 9.41
20
℃
DB
7.00
7.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
25
℃
DB
7.00
7.00
9.77
5.90
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
30
℃
DB
9.68
9.68
9.70
9.08 17.98 7.22 23.65 5.87
0.00
0.00
0.00
0.00
35
℃
DB
12.26 12.26 12.27 12.27 17.69 10.29 23.32 8.94 27.22 7.97 31.47 6.93
40
℃
DB
14.57 14.57 14.59 14.59 17.20 13.20 22.45 11.82 26.28 10.81 30.19 9.72
(kW)
Air flow
(m
3
/min)
-10
℃
WB
-5
℃
WB
0
℃
WB
4
℃
WB
8
℃
WB
12
℃
WB
-10
℃
DB
19.90
0.00
0.00
0.00
0.00
0.00
-5
℃
DB
17.74
17.75
0.00
0.00
0.00
0.00
0
℃
DB
15.98
15.99
16.00
0.00
0.00
0.00
4
℃
DB
13.53
13.54
13.55
13.56
0.00
0.00
8
℃
DB
11.15
11.16
11.16
11.17
11.18
0.00
12
℃
DB
8.52
8.53
8.53
8.54
8.54
8.55
16
℃
DB
6.14
6.15
6.15
6.16
6.16
6.17
20
℃
DB
4.06
4.06
4.07
4.07
4.07
4.07
-10
℃
DB
20.70
0.00
0.00
0.00
0.00
0.00
-5
℃
DB
18.45
18.46
0.00
0.00
0.00
0.00
0
℃
DB
16.62
16.63
16.64
0.00
0.00
0.00
4
℃
DB
14.07
14.08
14.09
14.10
0.00
0.00
8
℃
DB
11.59
11.60
11.61
11.62
11.62
0.00
12
℃
DB
8.86
8.87
8.87
8.88
8.88
8.89
16
℃
DB
6.41
6.42
6.42
6.43
6.44
6.44
20
℃
DB
4.21
4.21
4.21
4.21
4.22
4.22
-10
℃
DB
21.42
0.00
0.00
0.00
0.00
0.00
-5
℃
DB
19.09
19.10
0.00
0.00
0.00
0.00
0
℃
DB
17.19
17.21
17.22
0.00
0.00
0.00
4
℃
DB
14.56
14.57
14.58
14.59
0.00
0.00
8
℃
DB
12.00
12.00
12.01
12.02
12.03
0.00
12
℃
DB
9.17
9.18
9.18
9.19
9.19
9.20
16
℃
DB
6.66
6.66
6.67
6.68
6.68
6.69
20
℃
DB
4.35
4.36
4.36
4.36
4.36
4.37
Notes(1) These data show average statuses out of those possible to occur in the system control.
(2) Symbols are as follows
TC :Total cooling capacity (kW)
SHC :Sensible heat capacity (kW)
(3)
36
Air flow
(m
3
/min)
30
33
(Depending on controls, there may be ranges where the operation is not conducted continuously.
)
At heating operation outdoor temperature -5
℃
DB
-
-10
℃
DB,a wind of 10
℃
or lower in
temperature is blown out for 5
-
10minutes when starting a outdoor air processing unit after ending
a defrost operation.
30
33
36
Model
FDU1800FKXZE1
Heating mode
Cooling mode
Outdoor air
temperature
Outdoor air
temperature