6
GB
5. Confirmation of parts attached
•
This unit includes the following parts. Please check.
•
For usage methods, refer to item 10.2.
No.
1
Connecting pipe
ID ø19.05, OD ø22.2
<Gas side>
2
Connecting pipe
ID ø25.4, OD ø22.2
<Gas side>
3
Connecting elbow
ID ø28.58, OD ø28.58
<Gas side>
4
Connecting pipe
ID ø9.52, OD ø9.52
<Liquid side>
5
Connecting pipe
ID ø9.52, OD ø12.7
<Liquid side>
6
Connecting pipe
ID ø12.7, OD ø12.7
<Liquid side>
7
Connecting pipe
ID ø12.7, OD ø9.52
<Liquid side>
8
Connecting pipe
ID ø15.88, OD ø15.88
<Liquid side>
9
Connecting pipe
ID ø15.88, OD ø12.7
<Liquid side>
P200
1
1
P250
1
1
1
P300
1
1
1
P350
1
1
1
P400
1
1
1
P450
1
1
P500
1
1
6. Space required around unit
1
In case of single installation
• Secure enough space around the unit as shown in the figure.
• If the wall height exceeds the height limit, widen the space labeled "L" and "W" by the amount that exceeds the limit (labeled <h> in the figure).
[Fig. 6.0.1]
(1) Walls are lower than the height limit.
500
450
L
W
W
Should be shorter than the unit height
Should be shorter than the unit height
Condition
L
W
Minimum space behind the unit
100
50
Minimum space on both sides of the unit
300
15
(2) If the wall height (H) of the front, rear or side exceeds the wall height restriction
h
500
500
500
450 + h
450 + h
450 + h
L
W
W
h
L
W
W
h
h
h
L
W
W
h
Should be shorter than the unit height
Should be shorter than the unit height
Should be shorter than the unit height
Should be shorter than the unit height
Should be shorter than the unit height
Should be shorter than the unit height
Condition
L
W
Minimum space behind the unit
100 + h
50 + h
Minimum space on both sides of the unit
300 + h
15 + h
(3) If there are obstacles at the upper part of the unit
240
45°
50
1000
Air deflector grills
(field supplied)
(Unit : mm)