95
OCH754A
OPERATING PROCEDURE
PHOTOS/FIGURES
4. Removing the thermistor <2-phase pipe> (TH6) and
thermistor <Ambient>(TH7)
(1) Remove the service panel. (See Photo 1)
(2) Remove the top panel. (See Photo 1)
(3) Disconnect the connectors TH7/6 (red) on the controller cir-
cuit board in the electrical parts box.
Loosen fasteners for lead wires in the electrical parts box.
(4) Loosen the clamp for lead wires in the rear of the electrical
parts box.
(5) Pull out the thermistor <2-phase pipe> (TH6) and thermis-
tor <Ambient> (TH7) from the sensor holder.
Note: When replacing thermistor <2-phase pipe> (TH6) or
thermistor <Ambient> (TH7), replace it together.
Photo 5
Clamps
Heat exchanger
Thermistor
<2-phase pipe>
(TH6)
Electrical parts
box
Sensor holder
Photo 6
Lead wire of thermistor
<Ambient> (TH7)