CEILING CASSETTE
B-4
S series
600
o
600
CEILING
CASSETTE
SPECIFICA
TIONS
B.1.1 SPECIFICATIONS
Model Name
Indoor Unit
SLZ-KA25VA(L)
SLZ-KA35VA(L)
SLZ-KA50VA(L)
Outdoor Unit
SUZ-KA25VA
SUZ-KA35VA
SUZ-KA50VA
Power Supply
Source
Outdoor power supply
Out
V
230
230
230
Phase
Single
Single
Single
Hz
50
50
50
In
V
-
-
-
Phase
-
-
-
Hz
-
-
-
Refrigerant
R410A
R410A
R410A
Cooling
Capacity
Rated
kW
2.5
3.5
4.6
Max.
kW
3.2
3.9
5.2
Min.
kW
0.9
1.0
1.1
SHF
Rated
0.86
0.77
0.68
Total Input
Rated
kW
0.690
1.060
1.630
EER
3.62
3.30
2.82
EEL RANK
A
A
C
Heating
Capacity
Rated
kW
3.0
4.0
5.0
Max.
kW
4.5
5.0
6.5
Min.
kW
0.9
0.9
0.9
Total Input
Rated
kW
0.830
1.100
1.550
COP
3.61
3.64
3.22
EEL RANK
A
A
C
Operating Current(max)
A
8.5
9.6
16.7
Indoor
Unit
Input
Rated
kW
0.075 0.085 0.085
Operating
Current(max)
A
0.4 0.4 0.7
Dimensions
Height
mm
235
235
235
Width
mm
570
570
570
Depth
mm
570
570
570
Weight
kg
17 17 17
Air
Volume
Low
m³/min.
8.0 8.0 8.0
Mid2
m³/min.
-
-
-
Mid
m³/min.
9.0 9.0 9.0
Hi
m³/min.
10.0 11.0 11.0
External Static Pressure
Pa
-
-
-
Sound Level
Low
dB(A)
28
29
30
Mid2
dB(A)
-
-
-
Mid
dB(A)
31
33
34
Hi
dB(A)
37
38
39
Outdoor Unit
Dimensions
Height
mm
550
550
850
Width
mm
800
800
840
Depth
mm
285
285
330
Weight
kg
30
33
53
Air Volume
Cooling
Rated
m³/min.
34.3
33.4
49.0
Heating
Rated
m³/min.
32.3
33.4
49.0
Sound Level
Cooling
Rated
dB(A)
46
47
53
Silent
dB(A)
-
-
-
Heating
Rated
dB(A)
46
48
55
Operating Current(max)
A
8.2
9.2
16.0
Breaker Size
A
10
10
20
Ext. Piping
Diameter
Liquid
mm
6.35
6.35
6.35
Gas
mm
9.52
9.52
12.7
Max. Length
Out-In
m
20
20
30
Max. Height
Out-In
Below Indoor
m
12
12
30
Above Indoor
m
12
12
30
Guranteed
Operation
Range
Out
Cooling
Upper Limit.
°C
+46
+46
+43
Lower Limit.
°C
-10
-10
-15
Heating
Upper Limit.
°C
+24
+24
+24
Lower Limit.
°C
-10
-10
-10