18
2 SPECIFICATIONS
2.1 Performance Specifications
RTD input module
*1 An usable resistance temperature detector is 3-wire type only. A resistance temperature detector of 2-wire type or 4-wire type cannot be
used.
*2 When a value outside the input range is input from a resistance temperature detector, the value is regarded as the maximum value or
minimum value of the input range.
*3 The accuracy when a resistance temperature detector is connected, refer to the following.
Page 42 Accuracy of the RTD input module
*4 This conversion speed is the time required to store a measured temperature value into the buffer memory in sampling processing.
*5 A count more than 50000 times causes Number of writes to offset/gain settings reach limit error (error code: 1080H).
Item
Specifications
Model
R60RD8-G
Number of analog input channels
8 channels
Output
Measured temperature value
16-bit signed binary value (-2000 to 8500)
Scaling value
16-bit signed binary value
Usable resistance temperature detector
Pt100 (JIS C 1604-2013, IEC 751:1983)
JPt100 (JIS C 1604-1981)
Ni100 (DIN 43760 1987)
Pt50 (JIS C 1604-1981)
Temperature
measuring range
Pt100
-200 to 850
JPt100
-180 to 600
Ni100
-60 to 250
Pt50
-200 to 650
Output current for temperature detection
1.0mA or lower
Conversion
accuracy
Pt100
-200 to 850
0.8
(ambient temperature: 25
5
),
2.4
(ambient temperature: 0 to 55
)
-20 to 120
0.3
(ambient temperature: 25
5
),
1.1
(ambient temperature: 0 to 55
)
0 to 200
0.4
(ambient temperature: 25
5
),
1.2
(ambient temperature: 0 to 55
)
JPt100
-180 to 600
0.8
(ambient temperature: 25
5
),
2.4
(ambient temperature: 0 to 55
)
-20 to 120
0.3
(ambient temperature: 25
5
),
1.1
(ambient temperature: 0 to 55
)
0 to 200
0.4
(ambient temperature: 25
5
),
1.2
(ambient temperature: 0 to 55
)
Ni100
-60 to 250
0.4
(ambient temperature: 25
5
),
1.2
(ambient temperature: 0 to 55
)
Pt50
-200 to 650
0.8
(ambient temperature: 25
5
),
2.4
(ambient temperature: 0 to 55
)
Resolution
0.1
Conversion speed
10ms/channel
Isolation method
Between RTD input channel and
programmable controller power supply
Transformer isolation
Between RTD input channels
Transformer isolation
Withstand voltage
Between RTD input channel and
programmable controller power supply
500VACrms for 1 minute
Between RTD input channels
1000VACrms for 1 minute
Insulation
resistance
Between RTD input channel and
programmable controller power supply
500VDC 10M
or higher
Between RTD input channels
500VDC 10M
or higher
Disconnection detection
Built-in
Number of offset/gain settings
50000 times maximum
Number of occupied I/O points
16 points (I/O assignment: Intelligent 16 points)
External interface
40-pin connector
Applicable wire
size
When A6CON1 and A6CON4 are used
0.088mm
2
to 0.3mm
2
(28 to 22 AWG) (stranded wire)
When A6CON2 is used
0.088mm
2
to 0.24mm
2
(28 to 24 AWG) (stranded wire)
Connector for external devices
A6CON1, A6CON2, A6CON4 (sold separately)
Internal current consumption (5VDC)
0.35A
External
dimensions
Height
106mm
Width
27.8mm
Depth
110mm
Weight
0.19kg