CN2
Connect to the outdoor controller circuit board (CN2)
1
–
5
:
Outdoor power circuit board
→
Transmitting signal
to the outdoor controller circuit board (0–5 V DC)
2
–
5
: Zero cross signal (0–5 V DC)
3
–
4
: Not used
6
–
5
: 16 V DC
7
–
5
: 16 V DC
1
,
2
,
6
,
7
: +
5
: –
]
[
LI, NI
Voltage of 230 V AC is
input (Connect to the
terminal block (TB1))
U, V, W
Connect to the com-
pressor (MC)
Voltage among phases:
5 to 180 V AC
CN4
Connect from the
outdoor controller
circuit board
(CN4)
TB1A, TB3A, TB1B,
TB3B
Connect to DCL
E2, EI, E3, E4
Connect to earth
CN6
Thermistor
<Heat sink> (TH8)
CNDC
280–380 V DC (
1
: +,
3
−)
Connect to the out-
door controller circuit
board (CNDC)
N1
N
L
P1
N2
W2
V2
U2
P2
N3
W3
V3
U3
P3
68
Outdoor power circuit board
PUZ-ZM60VHA
PUZ-ZM71VHA
Brief Check of DIP-IPM and DIODE MODULE
Usually, they are in a state of being short-circuited if they are broken.
Measure the resistance in the following points (connectors, etc.). If they
are short-circuited, it means that they are broken.
1. Check of DIP-IPM
2. Check of DIODE MODULE
Note: The marks,
shown in the diagram are not actually printed on the board.
CNAC1, CNAC2
230 V AC
Connect to the out-
door controller circuit
board (CNAC)
IC600
DIP-IPM
IC500
DIP-IPM
P2
- U2 ,
P2
- V2 ,
P2
- W2 ,
N2
- U2 ,
N2
- V2 ,
N2
- W2
P3 - U3 , P3 - V3 , P3 - W3 , N3 - U3 , N3 - V3 , N3 - W3
P1 -
L
, P1 -
N
,
L
- N1 ,
N
- N1
L
,
N
, N1 ,
N2
, N3 , P1 ,
P2
, P3 , U2 , U3 , V2 , V3 , W2 , and W3
OCH653