13
OCH737
4
SPECIFICATIONS
Service Ref.
PUZ-M200YKA.UK
PUZ-M250YKA.UK
OUTDOOR UNIT
Power supply (phase, cycle, voltage)
3 phase 50 Hz, 400 V
Max. current
A
22.5
External finish
Munsell 3Y 7.8/1.1
Refrigerant control
Linear Expansion Valve
Compressor
Hermetic
Model
AVB52FBAMT
Motor output
kW
3.8
Starter type
Inverter
Protection devices
HP switch
Comp surface thermo
Over current detection
Thermal protector
Crankcase heater
W
—
Heat exchanger
Plate fin coil
Fan
Fan (drive) o No.
Propeller fan o 2
Fan motor output
kW
0.200 + 0.200
Airflow
m
3
/min(CFM)
140 (4,940)
Defrost method
Reverse cycle
Sound pressure level Cooling
dB
58
59
Heating
dB
60
62
Dimensions
W
mm (inch)
1,050 (41-5/16)
D
mm (inch)
330 + 40 (13+1-9/16)
H
mm (inch)
1,338 (52-11/16)
Weight
kg (lb)
129 (284)
138 (304)
Refrigerant
R32
Charge
kg (lb)
5.6 (12.3)
6.8 (15.0)
Oil (Model)
L
2.30 (FW68S)
REFRIGERANT
PIPING
Pipe size O.D.
Liquid
mm (inch)
9.52 (3/8)
12.7 (1/2)
Gas
mm (inch)
25.4 (1)
25.4 (1)
Connection method
Indoor side
Flared
Outdoor side
Flared & Brazing
Between the indoor &
outdoor unit
Height difference
Maximum 30 m
Piping length
Maximum 70 m