–106–
1) Total capacity of indoor units in the
same refrigerant system exceeds
the following:
2) Erroneous setting of OC model se-
lector switch (SW3-10).
1) The Indoor unit model name (model
code) connected is not connectable.
Connectable range.....20~250
2) Erroneous setting of the switch
(SW2) for setting of model name of
Indoor unit connected.
1) Number of unit connected to termi-
nal block (TB3) for outdoor/indoor
transmission line exceeds limita-
tions given be-lows:
Item
Limitation
1
Total of
1~15 (PURY-80(-A))
Indoor unit
1~16 (PURY-100(-A))
2
Total of Indoor
unit & RC
1~35
3
Total of BC
1
controller
(3)
System error
Checking
code
7100
7101
7102
Meaning, detecting method
Cause
Checking method & Countermeasure
Total capacity error
Total capacity of indoor units in
the same refrigerant system ex-
ceeds limitations.
Trouble source:
Outdoor unit
Capacity code error
Error display at erroneous con-
nection of Indoor unit of which
model name can not be con-
nected.
Trouble source :
Outdoor unit
Indoor unit
Connected unit count over
Number of units connected in the
same refrigerant system exceeds
limitations.
Trouble source:
Outdoor unit
a) Check for the model total (capacity cord total) of
indoor units connected.
b) Check whether indoor unit capacity code (SW2)
is wrongly set.
For erroneous switch setting, modify it, turn off
power source of outdoor unit, and indoor unit
simultaneously for 5 minutes or more to modify
the switch for setting the model name (capacity
coad).
Check for the model selector switch (Dip switches
SW3-10 on outdoor unit control circuit) of OC.
a) Check for the model name of the Indoor unit
connected.
b) Check for the switch (SW2 if indoor controller
for setting of Indoor unit model name of gener-
ating address. When it is not agreed to the model
name, modify the capacity code while shutting
off the power source of Indoor unit.
*
The capacity of Indoor unit can be confirmed by
the self-diagnosios function (SW1 operation) of
Indoor unit.
a) Check whether the connection of units to the
terminal block for indoor/outdoor transmission
wiring (TB3) of outdoor unit is not exceeding the
limitation.
(See
1
~
2
left.)
b) Check for 2), 3), and 4).
c) Check for the connection of transmission wiring
to the terminal block for centralized control is
erroneously connected to the indoor/outdoor
transmission wiring terminal block (TB3).
Model
Total capacity Total capacity code
PURY-80(-A)
120
62
PURY-100(-A)
150
78
1
ON 100(-A)
OFF 80(-A)
2 3 4 5
SW3
6 7 8 9 10
.....
...
Summary of Contents for PURY-100TMU
Page 8: ... 7 Controller Box ...
Page 11: ... 10 G A board CNIPM1 CN15V1 CNDR1 CNE CNDC1 Power board ...
Page 13: ... 12 RELAY 10 board RELAY 4 board ...
Page 14: ... 13 2 Refrigerant Circuit Diagram and Thermal Sensor ...
Page 15: ... 14 3 Electrical Wiring Diagram 1 MC P N ...
Page 17: ... 16 3 CMB 108 1010NU F ...
Page 18: ... 17 4 CMB 1013 1016NU F ...
Page 71: ... 70 Motor Compressor G A board Red U V W N P White Blue Blue Capacitor C1 Red IPM ...