OPERATING PROCEDURE
PHOTOS/FIGURES
4. Disassembling the electrical parts box (VKM type)
(1) Disconnect all the connectors on the multi controller circuit board.
(2)
Remove 2 screws
1
which fix the plate holding the multi controller
circuit board and the electrical parts box. (See Photo 5)
(3) Remove the multi controller circuit board. (See Photo 5)
(4) Disconnect the M-NET power board connector on the
back plate of the controller circuit board.
(5) Disconnect the connectors of reactor on the back plate
of the electrical parts box. (See Photo 6)
(6) Remove 2 screws
2
on the back plate of the electrical
parts box. (See Photo 6)
(7) Remove the 3 reactors. (See Photo 6)
Note 1: When reassembling the electrical parts box,
make sure that the wirings are correct.
Note 2: When exchanging the reactor, make sure to
exchange all the 3 reactors.
Photo 5
Photo 6
5. Disassembling the electrical parts box (YKM type)
(1) Disconnect all the connectors on the multi controller circuit board.
(2)
Remove 2 screws
1
which fix the plate holding the multi
controller circuit board and the electrical parts box.
(3) Remove the multi controller circuit board. (See Photo 7.)
(4) Disconnect the M-NET power board connector on the
back plate of the controller circuit board.
(5) Disconnect all the connectors on the noise filter circuit
board. (See Photo 8)
(6)
Remove 9 supports on the noise filter circuit board. (See Photo 8)
(7) Remove the noise filter circuit board. (See Photo 8)
(8)
Remove the noise filter plate fixing screws. (See Photo 8)
(9) Disconnect the connectors of reactor on the bottom
plate of the electrical parts box. (See Photo 9)
(10) Remove 4 screws
2
on the bottom plate of the
electrical parts box. (See Photo 9)
(11) Remove the reactor. (See Photo 9)
Note : When reassembling the electrical parts box,
make sure that the wirings are correct.
Photo 7
Photo 8
Photo 9
M-NET power board*
1
(M-NET P.B.)
*
1
The M-NET power board is installed behind the multi controller circuit board.
M-NET power board*
(M-NET P.B.)
* The M-NET power board is installed behind the multi controller circuit board.
Screws
2
Electrical
parts box
Connectors
of Reactor
Reactor
Screws
2
Electrical
parts box
Reactor
Reactor
Connectors
of Reactor
Connectors
of Reactor
Connectors
of Reactor
Multi controller circuit
board (MULTI.B.)
Electrical
parts box
Screws
1
Screw
1
Multi controller circuit
board (MULTI.B.)
Electrical parts box
Noise filter circuit
board (N.F.)
Electrical parts box
Power
circuit board
(P.B)
Supports
Supports
Noise filter plate
fixing screws
Noise filter
circuit board
(N.F.)
Supports
Reactor
Power circuit
board*
2
(P.B)
Terminal
block (TB1)
Terminal
block (TB3)
Terminal
block (TB7)
Terminal
block (TB1)
Terminal
block (TB3)
Terminal
block (TB7)
Terminal
block (TB1B)
Connector of
Reactor
138
OCH668B