![Mitsubishi Electric PUHZ-W112VHA Service Manual Download Page 10](http://html.mh-extra.com/html/mitsubishi-electric/puhz-w112vha/puhz-w112vha_service-manual_239627010.webp)
10
OCH562D
3-2. STANDARD OPERATION DATA
Mode
Cooling (A35/W7)
Heating (A7/W35)
Total
Capacity
W
10,000
11,200
Input
kW
3.57
2.51
Electrical circuit
Outdoor unit
PUHZ-W112VHA
Phase, Hz
1, 50
Voltage
V
230
Current
A
15.8
11.1
Refrigerant circuit
Discharge pressure
MPa
2.63
2.08
Suction pressure
MPa
0.83
0.67
Discharge temperature
ºC
69
60
Condensing temperature
ºC
45
36
Suction temperature
ºC
9
6
W
ater
conditions
Flow volume
L/min
28.7
32.1
Outlet water temperature
ºC
7
35
Outdoor conditions
Intake air
temperature
D.B.
ºC
35
7
W.B.
ºC
24
6
The unit of pressure has been changed to MPa based on international SI system.
The conversion factor is: 1 (MPa) = 10.2 (kgf/cm