43
Outdoor power circuit board
PUHZ-SHW80VAA.UK
PUHZ-SHW112VAA.UK
PUHZ-SW75VAA.UK
PUHZ-SW100VAA.UK
PUHZ-SHW80VAA-BS.UK
PUHZ-SHW112VAA-BS.UK
PUHZ-SW75VAA-BS.UK
PUHZ-SW100VAA-BS.UK
CNAC1, CNAC2
230 V AC
Connect to the outdoor controller
circuit board (CNAC)
NI, LI
Voltage of 230 V AC is
input (Connect to the ter-
minal block (TB1))
EI, E4
Connect to the
earth
E2, E3
Connect to
the earth
CN4
Connect to the outdoor
controller circuit board (CN4)
CN2
Connect to the outdoor controller circuit board (CN2)
1
–
5
: Transmitting signal to outdoor controller circuit
board (0–5 V DC)
2
–
5
: Zero cross signal (0–5 V DC)
3
–
4
: 18 V DC
6
–
5
: 16 V DC
7
–
5
: 16 V DC
CNDC
280–380 V DC (
1
+,
3
−)
Connect to the outdoor
controller circuit board
(CNDC)
U/V/W
Connect to the compres-
sor (MC) Voltage among
phases: 10–180 V AC
N1
N
L
P1
N2
W2
V2
U2
P2
N3
W3
V3
U3
P3
Brief Check of DIP-IPM and DIODE MODULE
Usually, they are in a state of being short-circuited if they are broken.
Measure the resistance in the following points (connectors, etc.). If they
are short-circuited, it means that they are broken.
1. Check of DIP-IPM
2. Check of DIODE MODULE
Note: The marks,
shown in the diagram are not actually printed on the board.
P2 - U2 , P2 - V2 , P2 - W2 ,
N2
- U2 ,
N2
- V2 ,
N2
- W2
P3 - U3 , P3 - V3 , P3 - W3 , N3 - U3 , N3 - V3 , N3 - W3
P1 - L , P1 -
N
, L - N1 ,
N
- N1
L ,
N
, N1 ,
N2
, N3 , P1 , P2 , P3 , U2 , U3 , V2 , V3 , W2 , and W3
CN6
Thermistor
<Heat sink>
(TH8)
IC600
DIP-IPM
IC500
DIP-IPM
TB1A, TB2A, TB3A,
Connect to DCL
TB1B, TB2B, TB3B
Connect to DCL
OCH651