57
SW2 setting
Display detail
Explanation for display
Unit
:
0 to 255
(When the temperature is 100°C or more, hundreds
digit, tens digit and ones digit are displayed by
turns.)
(Example) When 150°C;
0.5 s 0.5 s 2 s
0 to 130
(When the temperature is 100°C or more, hundreds
digit, tens digit and ones digit are displayed by
turns.)
(Example) When 115°C;
0.5 s 0.5 s 2 s
Thermo-on time until error stops
0 to 999
0 to 999
(When it is 100 minutes or more, hundreds digit, tens
digit and ones digit are displayed by turns.)
(Example) When 415 minutes;
0.5 s 0.5 s 2 s
Indoor pipe temperature/Liquid
(TH2 (3))
Indoor 3
−39 to 88
−39 to 88
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
Indoor pipe temperature/Cond./Eva.
(TH5 (3))
Indoor 3
−39 to 88
−39 to 88
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
When there is no indoor unit, “00” is displayed.
50
1
:
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
:
Minute
:
15
1
15
4
Discharge superheat on error occurring
SHd
0 to 255
Cooling = TH4−T
63HS
Heating = TH4−T
63HS
Sub cool on error occurring SC
0 to 130
Cooling = T
63HS
−TH3
Heating = T
63HS
−TH2
The black square (
■
) indicates a switch position.
Comp. surface temperature (TH33)
−52 to 221
−52 to 221
(When the temperature is 0
:
or less, "–" and tem-
perature are displayed by turns.)
(When the discharge thermistor detects 100°C or
more, hundreds digit, tens digit, and ones digit are
displayed by turns.)
(Example) When 105
:
;
0.5 s 0.5 s 2 s
1
ON
2 3 4 5 6
1
05
: