Error Code
Abnormal point and detection method
Case
Judgment and action
U9
(4220)
Detailed
codes
To find out the detail history (latest) about U9 error, turn ON SW2-1, 2-2, 2-6.
Refer to 11-10.
01
Overvoltage error
• Increase in DC bus voltage to
RP35-71V: 420V
RP100-140V: 400V
RP100-250Y: 760V
1
Abnormal increase in power source
voltage
2
Disconnection of compressor wiring
3
Defective outdoor power circuit
board
4
Compressor has a ground fault.
1
Check the field facility for the power
supply.
2
Correct the wiring (U.V.W phase) to
compressor. Refer to 11-9 (Outdoor
power circuit board).
3
Replace outdoor power circuit board.
4
Check compressor for electrical insula-
tion. Replace compressor.
02
Undervoltage error
• Instantaneous decrease in DC
bus voltage to
RP35-140V: 200V
RP100-140Y: 350V
RP200/250Y: 400V
1
Decrease in power source voltage,
instantaneous stop.
2
Disconnection or loose connection
of CN52C on the outdoor power
circuit board/controller circuit board
(RP100-140V)
3
Disconnection or loose connection
of CN52C on the outdoor noise fi lter
circuit board/controller circuit board
(RP35-71V)
4
Defective converter drive circuit of
outdoor power circuit board (RP35-140V)
5
Defective 52C drive circuit in outdoor
power circuit board (RP100-140V/
RP100-250Y)
6
Defective 52C drive circuit in outdoor
noise fi lter circuit board (RP35-71V)
7
Defective outdoor converter circuit
board (RP100-140Y)
8
Disconnection or loose connection
of rush current protect resistor RS
(RP100-250Y)
9
Defective rush current protect
resistor RS (RP100-250Y)
0
Disconnection or loose connection of
main smoothing capacitor CB (RP100-
140V)/CB1,CB2 (RP100-250Y)
1
Disconnection or loose connection
of CN2 on the outdoor power circuit
board /controller circuit board
(RP100-140V)
2
Power circuit failure on DC supply for
18V DC output on outdoor controller
circuit board (RP100-140V)
1
Check the fi eld facility for the power
supply.
23
Check CN52C wiring. (RP35-140V)
4
Replace outdoor power circuit board.
(RP35-140V)
5
Replace outdoor power circuit board.
(RP100-140V/RP100-250Y)
6
Replace outdoor noise fi lter circuit
board. (RP35-71V)
7
Replace outdoor converter circuit board.
(RP100-140Y)
8
Check RS wiring. (RP100-250Y)
9
Replace RS. (RP100-250Y)
0
Check CB wiring. (RP100-140V)/Check
CB1,CB2 wiring. (RP100-250Y)
1
Check CN2 wiring. (RP100-140V)
2
Replace outdoor controller circuit board.
(RP100-140V)
04
Input current sensor error/
L1-phase open error
• Decrease in input current
through outdoor unit to 0.1A
only if operation frequency is
more than or equal to 40Hz
or compressor current is more
than or equal to 6A.
1
L1-phase open (RP100-250Y)
2
Disconnection or loose connection
between TB1 and outdoor noise fi lter
circuit board (RP35-71V/RP100-250Y)
3
Disconnection or loose connection
of CN5 on the outdoor power circuit
board/CNCT on the outdoor noise
fi lter board (RP35-71V/RP100-250Y)
4
Defective ACCT(AC current trans) on
the outdoor noise fi lter circuit board
(RP35-71V/RP100-250Y)
5
Defective input current detection
circuit of outdoor power circuit board
6
Defective outdoor controller circuit board
1
Check the fi eld facility for the power
supply. (RP100-250Y)
2
Check the wiring between TB1 and
outdoor noise fi lter circuit board (RP35-
71V/RP100-250Y)
3
Check CN5/CNCT wiring. (RP35-71V/
RP100-250Y)
4
Replace outdoor noise fi lter circuit
board. (RP35-71V/RP100-250Y)
5
Replace outdoor power circuit board.
6
Replace outdoor controller circuit board.
08
Abnormal power synchronous
signal
• No input of power synchronous
signal to power circuit board
• Power synchronous signal
of 44 Hz or less, or 65 Hz or
more is detected on power
circuit board.
1
Distortion of power source voltage,
Noise superimposition.
2
Disconnection or loose connection of
earth wiring
3
Disconnection or loose connection
of CN2 on the outdoor power circuit
board /controller circuit board
4
Defective power synchrous signal
circuit in outdoor controller circuit
board
5
Defective power synchrous signal
circuit in outdoor power circuit board
1
Check the fi eld facility for the power
supply.
2
Check earth wiring.
3
Check CN2 wiring.
4
Replace outdoor controller circuit board.
5
Replace outdoor power circuit board.
Continue to the next page.